标准速查

国际工业热泵标准与政策

覆盖中国、欧盟、美国与日本的工程速查,并汇集政策摘要、权威原始链接和工程计算器入口。

标准数据库:已核验的精选记录可用。下方政策记录与精选外部资源仍可使用。

标准列表

标准分类(中英对照) 标准号 标准名称(中英对照) 核心内容与适用范围(中英对照)
Showing a curated preview of verified standards. Full interactive filtering requires JavaScript.
安全与环保 (基础) GB/T 9237-2017
Refrigerating systems and heat pumps — Safety and environmental requirements
制冷系统和热泵 安全与环境要求
Identical to ISO 5149; effective text includes Amendment No. 2 (XG2-2020, effective 2021-07-01). Foundational safety and environmental requirements for heat-pump design, manufacture and installation.
安全与环保 (基础) GB/T 10891-2025
Refrigerating systems and heat pumps — Environmental adaptability requirements
(最新版) 制冷系统及热泵 环境适应性要求
Replaces GB/T 10891-1989; effective 2026-05-01 under SAC/TC 238. Defines environmental classes (temperature/humidity, corrosion, vibration, etc.) and test methods. Align type-test reports, site environmental declarations and warranty clauses with the new edition.
安全与环保 (基础) GB/T 4706.32-2024
Household and similar electrical appliances — Safety — Part 32: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers
(即将实施) 家用和类似用途电器的安全 第32部分:热泵、空调器和除湿机的特殊要求
Identical to IEC 60335-2-40:2022; fully replaces GB 4706.32-2012. Published 2024-07-24; effective 2026-08-01. Projects or certificates still referencing the 2012 edition should follow regulator notices and contract terms.
安全与环保 (基础) GB 25131-2010
Safety requirements for water chilling (heat pump) packages using the vapor-compression cycle
蒸气压缩循环冷水(热泵)机组 安全要求
Dedicated safety requirements for water chilling (heat pump) packages.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 18430.1-2024
Water chilling (heat pump) packages using the vapor-compression cycle — Part 1: Water chilling (heat pump) packages for industrial and commercial and similar application
(最新版) 蒸气压缩循环冷水(热泵)机组 第1部分:工业或商业用及类似用途的冷水(热泵)机组
Replaces GB/T 18430.1-2007; aligns with the SAC/TC238 chilled-water heat pump family for industrial and commercial use. Provides the fundamental framework for performance and type testing at low/medium temperature.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 10870-2014
The methods of performance test for water chilling (heat pump) packages using the vapor-compression cycle
蒸气压缩循环冷水(热泵)机组 性能试验方法
Fundamental performance test methods; normatively referenced by GB/T 18430.1 among others.
压缩式热泵 - 基础与中低温 (≤ 95°C) JB/T 4330-1999
Determination of noise emitted by refrigerating and air-conditioning equipment
制冷和空调设备噪声的测定
Industry noise measurement practice; still cited on legacy projects and type-test reports. New designs and certifications should prefer GB/T 9068-2025 where applicable.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 9068-2025
Determination of sound power levels of refrigerating and air-conditioning equipment — Sound pressure method
(最新版) 制冷与空调设备噪声声功率级的测定 声压法
Replaces GB/T 9068-1988; effective 2026-05-01. Sound power level determination for refrigerating systems, heat pumps, assemblies and components (hemi-anechoic/anechoic and engineering-grade free-field methods), aligned with type testing and site acceptance.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 19409-2013
Water (ground) source heat pumps
水(地)源热泵机组
Dedicated to water- and ground-source heat pumps; core norm for industrial use of waste water, geothermal energy and similar heat sources.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 21363-2017
Variable speed air-source heat pump (chiller) packages
转速可控型空气源热泵(冷水)机组
Addresses inverter-driven units: seasonal performance and operating flexibility requirements.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 18837-2026
Multi-split air-conditioning (heat pump) units
(最新版) 多联式空调(热泵)机组
Chinese recommended product standard, published 2026-04-30 and effective 2026-11-01; fully replaces the 2015 edition (ICS 27.200, CCS J 73). The openstd page, opened 2026-11-01, says in force. The national standards information platform, opened 2026-11-08, also says in force. Opened again on 2026-11-15, both the openstd page and the information platform say in force. Use this edition for selection, declared performance, type testing and procurement, and read it with GB/T 27941-2026 for application design and installation. Confirm scope and clauses against the normative text and the page cited.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 27941-2026
Design and installation requirements for multi-split air-conditioning (heat pump) systems
(最新版) 多联式空调(热泵)机组应用设计与安装要求
Published 2026-04-30 and effective 2026-11-01; fully replaces the 2011 edition (CCS J 73, ICS 27.200, SAC/TC 238). The openstd page, opened 2026-11-01, says in force. The national standards information platform, opened 2026-11-08, says in force. Opened 2026-11-01, that platform page still said not yet in force. Opened again on 2026-11-15, both the openstd page and the information platform say in force. The publication and effective dates match. Confirm scope and clauses against the normative text and the page cited.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 21362-2023
Heat pump water heaters for commercial and industrial and similar application
(最新版) 商业或工业用及类似用途的热泵热水机
Updated edition replacing GB 21362-2008; product standard for commercial and industrial heat-pump water heaters.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 25127.1-2020
Low ambient temperature air source heat pump (chiller) packages — Part 1: Heat pump (chiller) packages for industrial and commercial and similar application
(最新版) 低环境温度空气源热泵(冷水)机组 第1部分:工业或商业用及类似用途的热泵(冷水)机组
Replaces GB/T 25127.1-2010; oriented to cold-climate northern applications.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB 25127.2-2020
Low ambient temperature air source heat pump (chiller) packages — Part 2: Heat pump (chiller) packages for household and similar application
低环境温度空气源热泵(冷水)机组 第2部分:户用及类似用途的热泵(冷水)机组
Residential portion of the low-ambient air-source heat pump (chiller) family.
压缩式热泵 - 基础与中低温 (≤ 95°C) JB/T 15555-2026
Ultra-low ambient temperature air source heat pump (chiller) packages (latest)
(最新版) 超低环境温度空气源热泵(冷水)机组
Mechanical-industry product standard; published 2026-02-13; effective 2026-09-01 (ICS 27.200, CCS J73). Applies to motor-driven vapour-compression units that use air as the heat (or cool) source and can still produce hot or chilled water at outdoor temperatures down to −35 °C; covers type, basic parameters, technical requirements, test methods, inspection, marking and packaging. Complements GB/T 25127.1-2020 and NB/T 11505-2024 by extending the outdoor-temperature floor to −35 °C. Confirm scope against the normative text.
压缩式热泵 - 基础与中低温 (≤ 95°C) NB/T 11505-2024
Cascade air-source heat pump heating unit for commercial application
(最新版) 商用复叠式空气源热泵供暖机组
NEA industry standard; published 2024-05-24; effective 2024-11-24. Applies to motor-driven commercial cascade air-source heat pump heating units with nominal heating capacity above 35 kW, capable of delivering hot water not below 65 °C at outdoor temperatures not below −30 °C; covers classification, technical requirements, test methods, inspection rules, marking and transport.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 25861-2023
Water-source high temperature heat pump packages using the vapor-compression cycle
(最新版) 蒸气压缩循环水源高温热泵机组
Leading product standard for water-source high-temperature heat pumps in the Chinese market; central to industrial high-temperature hot water applications.
压缩式热泵 - 基础与中低温 (≤ 95°C) JB/T 12853-2016
Heat pump water heaters for industrial and similar purposes
工业用及类似用途的热泵热水机
Core industrial hot-water industry standard; defines “industrial-use” heat pumps with temperature ranges complementary to GB/T 25861.
压缩式热泵 - 基础与中低温 (≤ 95°C) GB/T 21087-2007
Air-to-air energy recovery equipment
空气-空气能量回收装置
Component standard commonly used in heat pump systems for air-side energy recovery.

英文行采用各法域正式题名(GB/EN/AHRI/JIS)或工程摘要;签约与执法适用仍以该法域正式出版物及合同文本为准。

工业高温热泵核心政策汇总表

政策名称 发布机构 发布时间 核心涉及领域 优惠条款与指导摘要
《推动热泵行业高质量发展行动方案》 发改环资等 2025年 工业热泵应用、园区节能 明确推动工业余热回收,鼓励行业场景拓展。
《节能装备高质量发展实施方案》 工信部等 2026年 高温热泵、工业装备 列为重点装备,支持跨临界 CO₂ 及蒸汽热泵攻关。
《关于更高水平更高质量做好节能降碳工作的意见》 国务院办公厅 2026年 节能降碳、技术推广 纳入节能技术装备推荐目录,加快推进高温热泵推广。
《碳达峰碳中和综合评价考核办法》 国务院办公厅 2026年 碳排放考核、能源转型 将热泵及分布式能源纳入指标体系,强化降碳动力。
《关于开展零碳工厂建设工作的指导意见》 五部门联合 2025年 零碳工厂、余热利用 鼓励余热回收与高效热泵一体化,支持燃煤锅炉替代。
《中国履行蒙特利尔议定书国家方案》 生态环境部等 2025年 制冷剂、天然工质 对高 GWP 氟利昂严控配额,倒逼天然工质(CO₂/R290)技术升级。
《关于开展重点行业节能降碳改造攻坚三年行动的通知》(发改环资〔2026〕698 号) 发改环资等五部门 2026 年 6 月 钢铁、电解铝、水泥、平板玻璃、甲醇、合成氨、煤电等九大行业 六大行业用能设备更新清单点名热泵;2026–2028 三年攻坚、应改尽改;符合条件项目中央投资最高 20% 补助;鼓励合同能源管理(EMC)。
《可再生能源消费最低比重目标和可再生能源电力消纳责任权重制度实施办法》(2026 年第 42 号令) 国家发展改革委、工业和信息化部、住房城乡建设部、交通运输部 2026 年 6 月(2026-08-01 施行) 重点用能行业绿电/非电消费、省级可再生能源消纳权重 建立「消费端刚性义务 + 消纳端属地责任」双轨制度;电力消费以绿证核算,非电含供热(制冷)等;钢铁、电解铝、水泥等重点行业纳入监测考核;未完成可通过绿证补充,逾期约谈通报并纳入信用记录。
《新型能源体系建设"十五五"规划》 国家发展改革委、国家能源局 2026 年 6 月(发改能源〔2026〕884 号) 热力系统转型、工业余热、园区供热、储热柔性调节 顶层规划明确加大余热回收与热泵推广,建设面向园区/城市的区域热力系统,布局储热储冷与热负荷柔性调节,推动零碳工厂/园区与工业清洁替代。

1. 产业技术与装备导向(支撑研发创新)

政策重心已从早期的「推广」转向「高质量、高效、高温度」的精细化供给。

  • 高温突破:国家明确支持突破高温热泵的技术壁垒,特别是针对工业用热需求(100–200 ℃),为高温压缩机与系统供应商布局高温技术提供政策底气。
  • 技术自主:《节能装备高质量发展实施方案》将高温热泵纳入重点,意味着在技术研发、实验室建设及关键项目申报上会有更多资源倾斜。

2. 「双碳」考核倒逼机制(支撑商业模式)

考核制度的精细化,是推动工业企业(B 端)主动替换传统能源的最强杠杆。

  • 考核压力:《碳达峰碳中和综合评价考核办法》明确了对地方和企业的能耗、碳排考核。企业若不进行技术改造,传统燃气/锅炉相关的碳合规成本可能持续上升。
  • 负成本逻辑:政策引导将碳减排转化为「碳资产」,使热泵运行不仅是节能,更可创造碳相关收益,为 EMC(合同能源管理)+ 碳资产管理 商业模式提供财务逻辑支撑。

3. 天然工质与绿色转型(支撑长远战略)

环保政策的强制性决定了未来的技术主流。

  • 配额限制:氟利昂制冷剂削减进度表明确,使以 CO₂、R290 为代表的天然工质热泵成为「必选项」而非「可选项」,与天然工质(含极寒复叠 CO₂ 采暖等)技术路线高度契合。

4. 零碳园区建设(支撑大型化战略)

针对工业集中供热的市场空间,政策提供了明确的园区示范路径。

  • 系统集成:零碳园区相关指导意见支持多能互补、余热耦合等系统性工程——不仅是卖设备,更是卖「园区级综合能源解决方案」,与大型系统集成思路一致。

5. 重点行业节能降碳改造攻坚三年行动(698 号文)

2026 年 6 月,发改环资等五部门联合印发九大重点行业节能降碳改造攻坚三年行动通知,附件行动计划在钢铁、电解铝、水泥、平板玻璃、甲醇/合成氨、煤电等六个行业的用能设备更新清单中,将热泵与电机、风机、水泵、锅炉等并列点名——工业热泵从「鼓励推广」进入「改造清单」语境。信息来源:国家发改委官网(发改环资〔2026〕698 号及附件)。本站解读仅供工程参考,不构成法律意见。

  • 装备清单地位:附件在钢铁、电解铝、水泥、平板玻璃、甲醇/合成氨、煤电六个行业均要求加快电机、风机、水泵、热泵、锅炉等用能设备更新升级,与 深度解读 1 的装备导向一脉相承——热泵已成为行业节能降碳改造的常规选项,而非可装可不装的附加项。
  • 典型应用场景:钢铁、化工侧重余热回收与余能发电配套热泵升级;甲醇/合成氨强调余热余压利用并推进用能系统电气化改造;煤电要求热泵更新升级,并推动热电联产热电解耦、储能储热耦合——对应工业高温/蒸汽热泵在流程供热、废热提温、区域供热等方向的工程切口。
  • 资金与商业模式:符合条件项目可按核定总投资 20% 获得中央投资补助(达能效标杆水平者优先);节能专用装备、技术改造、资源综合利用等税收优惠适用;改造减排量经核定可作新(改扩)建「两高」项目碳排放置换源;碳市场配额向先进企业倾斜;明确鼓励合同能源管理(EMC)——与 深度解读 2 的双碳考核与「负成本」逻辑相互强化。
  • 落地节奏:2026–2028 三年攻坚;2026 年 7 月底前省级节能主管部门报送总体方案与改造计划清单,九大行业企业应改尽改。到 2028 年底,工业重点行业能效标杆产能比例平均提高 20 个百分点(煤电力争 +15 个百分点),累计节能量 1 亿吨标煤以上、减排二氧化碳 2 亿吨以上——为工业热泵供应商与系统集成商形成可申报、可落地的近期项目池。

6. 可再生能源消费义务与绿证(42 号令)

2026 年 6 月,四部门联合公布 2026 年第 42 号令,建立可再生能源消费最低比重目标与省级电力消纳责任权重制度,自 2026 年 8 月 1 日起施行。对工业热泵而言,电气化供热从此与绿电消费、绿证核算直接挂钩——设备能效之外,还需同步规划电力来源与合规路径。信息来源:国家发改委答记者问(2026 年第 42 号令)。本站解读仅供工程参考,不构成法律意见。

  • 双轨制度框架:省级消纳责任权重(以物理消纳电量核算,不足可通过绿证补充)+ 重点用能行业消费最低比重(电力/非电两类)——落实《能源法》要求,将宏观双碳目标拆解为可量化、可考核的刚性约束;与 深度解读 2 的双碳考核逻辑一脉相承。
  • 工业热泵 × 绿电消费:热泵属用电侧电气化供热;企业绿电消费比例以考核年生产电量对应绿证核算——热泵项目方案需同步规划 PPA/绿证采购,否则「设备节能」难抵消「电网碳强度」考核压力(亦可对照本站 热泵小知识 中灰电 vs 绿电讨论)。
  • 非电消费与供热(制冷):办法首次将非电利用纳入最低比重考核体系,范围含可再生能源供热(制冷);工业废热热泵、园区耦合供热等可纳入长期合规叙事,但官方答记者问明确非电统计核算体系尚在完善,初期分行业、分品类稳妥推进,待条件成熟后再全面纳入监测考核。
  • 与 698 号文协同:钢铁、电解铝、水泥等与 698 改造清单行业高度重叠——设备更新(热泵)+ 绿电消费(42 号令)构成组合合规路径;未完成指标可在公布后 3 个月内通过绿证交易补充,逾期约谈通报并依法纳入信用记录——强化 专家建议 中「从鼓励到考核」的叙事。

7. 新型能源体系「十五五」规划(884 号文)

2026 年 6 月 13 日,国家发展改革委、国家能源局印发《新型能源体系建设"十五五"规划》(发改能源〔2026〕884 号,国务院同意)。规划第四章「构建绿色低碳的能源消费体系」专章提出推动热力系统绿色低碳转型——加大余热回收利用力度、因地制宜加大热泵推广应用,并布局面向城市与园区的区域热力系统、储热储冷与热负荷柔性调节。信息来源:国家能源局官网(884 号文)。本站解读仅供工程参考,不构成法律意见。

  • 顶层定位:从专项推广到体系规划:热力系统绿色低碳转型写入能源领域「十五五」专项规划,与新型电力系统、非化石能源规模扩大并列。在能源顶层规划中,加大余热回收利用与因地制宜加大热泵推广应用首次并列提出——工业热泵由部委行动方案层面的「鼓励应用」上升为能源体系建设的标配路径。
  • 工业场景:余热回收 + 清洁替代:「加大余热回收利用力度」直接对应工业废水/废气/流程余热经热泵制备高温蒸汽或热风——与 深度解读 1 的高温突破、深度解读 5 的改造清单一脉相承。「优化工业领域能源清洁替代路径、稳步压减燃煤自备电厂」为工业锅炉/自备电厂替代打开政策空间;规划同步推动钢铁、石化、建材等传统产业电气化(电锅炉、电加热、电辅热炉窑等),工业热泵是更高能效的电气化选项。「推动零碳工厂和园区建设」将园区级工业热泵与余热耦合纳入示范主线(见 深度解读 4)。
  • 系统级利好:园区热力、储热、柔性调节:「面向城市、园区的区域热力系统」及非化石热源与既有热网融合,支持园区集中式/分布式工业热泵与余热共享网络。「多尺度储热储冷设施」「热负荷柔性调节」「热电协同、热–电–气联合调度」使工业蒸汽热泵 + 储热可参与峰谷调节、消纳绿电——与 深度解读 6 的绿电消费逻辑形成设备 + 电力 + 储热组合路径。
  • 2030 目标与政策协同:2030 年非化石能源消费比重达 25%、新能源发电量占比达 30%、碳排放双控全面实施——工业热泵项目的绿电/绿证策划必要性上升。与《推动热泵行业高质量发展行动方案》、698 号文、42 号令、节能装备方案形成「顶层规划 → 行业方案 → 改造清单 → 消费考核」政策链;对外沟通可强调规划将工业热泵纳入能源消费体系主干,而非孤立节能技术(见 专家建议)。

专家建议:政策逻辑要点

工业热泵政策 · 对外沟通提示

汇报与对外沟通时,可重点强调 「政策从『鼓励』向『考核』转变」:以往节能改造主要为降成本,现为应对地方碳排放强度等强制考核。该转变极大缩短工业客户决策周期,行业战略布局正处政策激励释放的前夜。

常见问题

本页用来做什么?

工业热泵相关标准、政策入口与精选外链的中英速查地图——不能替代购买或引用正式标准文本。

如何查中国 / 欧盟 / 美国 / 日本标准?

在「标准」表格中定位常见 GB/T、EN、ASHRAE/AHRI、JIS 条目,再打开发布方或国家标准目录核对现行版本。

工业热泵政策摘要在哪里?

滚动到「政策」区块,可见国家行动方案、碳评估与天然工质方向的摘要及来源链接。

这算法律或合规意见吗?

不是。本页仅为工程导向说明。采购、安全、F-gas 或许可决策须以监管原文与合格顾问意见为准。