標準速查
國際工業熱泵標準與政策
覆蓋中國、歐盟、美國與日本的工程速查,並彙集政策摘要、權威原始鏈接和工程計算器入口。
標準數據庫:已覈驗的精選記錄可用。下方政策記錄與精選外部資源仍可使用。
標準列表
| 標準分類(中英對照) | 標準號 | 標準名稱(中英對照) | 核心內容與適用範圍(中英對照) |
|---|---|---|---|
| 以下爲已覈驗標準的預覽片段。完整交互篩選需要啓用 JavaScript。 | |||
| 安全与环保 (基础) | GB/T 9237-2017 | Refrigerating systems and heat pumps — Safety and environmental requirements 制冷系统和热泵 安全与环境要求 |
Identical to ISO 5149; effective text includes Amendment No. 2 (XG2-2020, effective 2021-07-01). Foundational safety and environmental requirements for heat-pump design, manufacture and installation. |
| 安全与环保 (基础) | GB/T 10891-2025 | Refrigerating systems and heat pumps — Environmental adaptability requirements (最新版) 制冷系统及热泵 环境适应性要求 |
Replaces GB/T 10891-1989; effective 2026-05-01 under SAC/TC 238. Defines environmental classes (temperature/humidity, corrosion, vibration, etc.) and test methods. Align type-test reports, site environmental declarations and warranty clauses with the new edition. |
| 安全与环保 (基础) | GB/T 4706.32-2024 | Household and similar electrical appliances — Safety — Part 32: Particular requirements for electrical heat pumps, air-conditioners and dehumidifiers (即将实施) 家用和类似用途电器的安全 第32部分:热泵、空调器和除湿机的特殊要求 |
Identical to IEC 60335-2-40:2022; fully replaces GB 4706.32-2012. Published 2024-07-24; effective 2026-08-01. Projects or certificates still referencing the 2012 edition should follow regulator notices and contract terms. |
| 安全与环保 (基础) | GB 25131-2010 | Safety requirements for water chilling (heat pump) packages using the vapor-compression cycle 蒸气压缩循环冷水(热泵)机组 安全要求 |
Dedicated safety requirements for water chilling (heat pump) packages. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 18430.1-2024 | Water chilling (heat pump) packages using the vapor-compression cycle — Part 1: Water chilling (heat pump) packages for industrial and commercial and similar application (最新版) 蒸气压缩循环冷水(热泵)机组 第1部分:工业或商业用及类似用途的冷水(热泵)机组 |
Replaces GB/T 18430.1-2007; aligns with the SAC/TC238 chilled-water heat pump family for industrial and commercial use. Provides the fundamental framework for performance and type testing at low/medium temperature. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 10870-2014 | The methods of performance test for water chilling (heat pump) packages using the vapor-compression cycle 蒸气压缩循环冷水(热泵)机组 性能试验方法 |
Fundamental performance test methods; normatively referenced by GB/T 18430.1 among others. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | JB/T 4330-1999 | Determination of noise emitted by refrigerating and air-conditioning equipment 制冷和空调设备噪声的测定 |
Industry noise measurement practice; still cited on legacy projects and type-test reports. New designs and certifications should prefer GB/T 9068-2025 where applicable. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 9068-2025 | Determination of sound power levels of refrigerating and air-conditioning equipment — Sound pressure method (最新版) 制冷与空调设备噪声声功率级的测定 声压法 |
Replaces GB/T 9068-1988; effective 2026-05-01. Sound power level determination for refrigerating systems, heat pumps, assemblies and components (hemi-anechoic/anechoic and engineering-grade free-field methods), aligned with type testing and site acceptance. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 19409-2013 | Water (ground) source heat pumps 水(地)源热泵机组 |
Dedicated to water- and ground-source heat pumps; core norm for industrial use of waste water, geothermal energy and similar heat sources. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 21363-2017 | Variable speed air-source heat pump (chiller) packages 转速可控型空气源热泵(冷水)机组 |
Addresses inverter-driven units: seasonal performance and operating flexibility requirements. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 18837-2026 | Multi-split air-conditioning (heat pump) units (最新版) 多联式空调(热泵)机组 |
Chinese recommended product standard, published 2026-04-30 and effective 2026-11-01; fully replaces the 2015 edition (ICS 27.200, CCS J 73). The openstd page, opened 2026-11-01, says in force. The national standards information platform, opened 2026-11-08, also says in force. Opened again on 2026-11-15, both the openstd page and the information platform say in force. Use this edition for selection, declared performance, type testing and procurement, and read it with GB/T 27941-2026 for application design and installation. Confirm scope and clauses against the normative text and the page cited. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 27941-2026 | Design and installation requirements for multi-split air-conditioning (heat pump) systems (最新版) 多联式空调(热泵)机组应用设计与安装要求 |
Published 2026-04-30 and effective 2026-11-01; fully replaces the 2011 edition (CCS J 73, ICS 27.200, SAC/TC 238). The openstd page, opened 2026-11-01, says in force. The national standards information platform, opened 2026-11-08, says in force. Opened 2026-11-01, that platform page still said not yet in force. Opened again on 2026-11-15, both the openstd page and the information platform say in force. The publication and effective dates match. Confirm scope and clauses against the normative text and the page cited. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 21362-2023 | Heat pump water heaters for commercial and industrial and similar application (最新版) 商业或工业用及类似用途的热泵热水机 |
Updated edition replacing GB 21362-2008; product standard for commercial and industrial heat-pump water heaters. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 25127.1-2020 | Low ambient temperature air source heat pump (chiller) packages — Part 1: Heat pump (chiller) packages for industrial and commercial and similar application (最新版) 低环境温度空气源热泵(冷水)机组 第1部分:工业或商业用及类似用途的热泵(冷水)机组 |
Replaces GB/T 25127.1-2010; oriented to cold-climate northern applications. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB 25127.2-2020 | Low ambient temperature air source heat pump (chiller) packages — Part 2: Heat pump (chiller) packages for household and similar application 低环境温度空气源热泵(冷水)机组 第2部分:户用及类似用途的热泵(冷水)机组 |
Residential portion of the low-ambient air-source heat pump (chiller) family. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | JB/T 15555-2026 | Ultra-low ambient temperature air source heat pump (chiller) packages (latest) (最新版) 超低环境温度空气源热泵(冷水)机组 |
Mechanical-industry product standard; published 2026-02-13; effective 2026-09-01 (ICS 27.200, CCS J73). Applies to motor-driven vapour-compression units that use air as the heat (or cool) source and can still produce hot or chilled water at outdoor temperatures down to −35 °C; covers type, basic parameters, technical requirements, test methods, inspection, marking and packaging. Complements GB/T 25127.1-2020 and NB/T 11505-2024 by extending the outdoor-temperature floor to −35 °C. Confirm scope against the normative text. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | NB/T 11505-2024 | Cascade air-source heat pump heating unit for commercial application (最新版) 商用复叠式空气源热泵供暖机组 |
NEA industry standard; published 2024-05-24; effective 2024-11-24. Applies to motor-driven commercial cascade air-source heat pump heating units with nominal heating capacity above 35 kW, capable of delivering hot water not below 65 °C at outdoor temperatures not below −30 °C; covers classification, technical requirements, test methods, inspection rules, marking and transport. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 25861-2023 | Water-source high temperature heat pump packages using the vapor-compression cycle (最新版) 蒸气压缩循环水源高温热泵机组 |
Leading product standard for water-source high-temperature heat pumps in the Chinese market; central to industrial high-temperature hot water applications. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | JB/T 12853-2016 | Heat pump water heaters for industrial and similar purposes 工业用及类似用途的热泵热水机 |
Core industrial hot-water industry standard; defines “industrial-use” heat pumps with temperature ranges complementary to GB/T 25861. |
| 压缩式热泵 - 基础与中低温 (≤ 95°C) | GB/T 21087-2007 | Air-to-air energy recovery equipment 空气-空气能量回收装置 |
Component standard commonly used in heat pump systems for air-side energy recovery. |
英文行採用各法域正式題名(GB/EN/AHRI/JIS)或工程摘要;簽約與執法適用仍以該法域正式出版物及合同文本爲準。
工業高溫熱泵核心政策彙總表
| 政策名稱 | 發佈機構 | 發佈時間 | 核心涉及領域 | 優惠條款與指導摘要 |
|---|---|---|---|---|
| 《推動熱泵行業高質量發展行動方案》 | 發改環資等 | 2025 | 工業熱泵應用、園區節能 | 明確推動工業餘熱回收,鼓勵行業場景拓展。 |
| 《節能裝備高質量發展實施方案》 | 工信部等 | 2026 | 高溫熱泵、工業裝備 | 列爲重點裝備,支持跨臨界 CO₂ 及蒸汽熱泵攻關。 |
| 《關於更高水平更高質量做好節能降碳工作的意見》 | 國務院辦公廳 | 2026 | 節能降碳、技術推廣 | 納入節能技術裝備推薦目錄,加快推進高溫熱泵推廣。 |
| 《碳達峯碳中和綜合評價考覈辦法》 | 國務院辦公廳 | 2026 | 碳排放考覈、能源轉型 | 將熱泵及分佈式能源納入指標體系,強化降碳動力。 |
| 《關於開展零碳工廠建設工作的指導意見》 | 五部門聯合 | 2025 | 零碳工廠、餘熱利用 | 鼓勵餘熱回收與高效熱泵一體化,支持燃煤鍋爐替代。 |
| 《中國履行蒙特利爾議定書國家方案》 | 生態環境部等 | 2025 | 製冷劑、天然工質 | 對高 GWP 氟利昂嚴控配額,倒逼天然工質(CO₂/R290)技術升級。 |
| Notice on the Three-Year Energy-Saving and Carbon-Reduction Retrofit Drive in Key Industries (Doc. 698) | 發改環資等五部門 | Jun 2026 | 鋼鐵、電解鋁、水泥、平板玻璃、甲醇、合成氨、煤電等九大行業 | 六大行業用能設備更新清單點名熱泵;2026–2028 三年攻堅、應改盡改;符合條件項目中央投資最高 20% 補助;鼓勵合同能源管理(EMC)。 |
| Measures for Renewable Energy Consumption Minimum Share and Renewable Electricity Consumption Responsibility Weight (Order 42) | 國家發展改革委、工業和信息化部、住房城鄉建設部、交通運輸部 | Jun 2026 (effective 1 Aug 2026) | 重點用能行業綠電/非電消費、省級可再生能源消納權重 | 建立「消費端剛性義務 + 消納端屬地責任」雙軌制度;電力消費以綠證覈算,非電含供熱(製冷)等;鋼鐵、電解鋁、水泥等重點行業納入監測考覈;未完成可通過綠證補充,逾期約談通報並納入信用記錄。 |
| New Energy System Construction "15th Five-Year" Plan | 國家發展改革委、國家能源局 | Jun 2026 (Doc. 884) | 熱力系統轉型、工業餘熱、園區供熱、儲熱柔性調節 | 頂層規劃明確加大余熱回收與熱泵推廣,建設面向園區/城市的區域熱力系統,佈局儲熱儲冷與熱負荷柔性調節,推動零碳工廠/園區與工業清潔替代。 |
1. 產業技術與裝備導向(支撐研發創新)
政策重心已從早期的「推廣」轉向「高質量、高效、高溫度」的精細化供給。
- High-temperature breakthrough: National policy explicitly supports breaking high-temperature heat pump barriers, especially for industrial heat in the 100–200 °C range—policy backing for high-temperature compressor and system suppliers.
- Technology autonomy: The energy-saving equipment plan elevates high-temperature heat pumps to priority status, implying more resources for R&D, laboratories, and key project applications.
2. 「雙碳」考覈倒逼機制(支撐商業模式)
Finer assessment rules are the strongest lever for industrial users (B2B) to replace legacy heat supply.
- Assessment pressure: The comprehensive carbon peaking/neutrality assessment framework clarifies energy and carbon obligations for local governments and enterprises. Without retrofits, costs tied to gas, boilers, and carbon compliance are likely to rise.
- “Negative-cost” logic: Policy steers carbon reduction toward tradable carbon assets, so heat pump operation is not only energy saving but can generate carbon-related value—supporting EMC (energy performance contracting) plus carbon asset management business models.
3. 天然工質與綠色轉型(支撐長遠戰略)
環保政策的強制性決定了未來的技術主流。
- Quota limits: Fluorinated refrigerant phase-down schedules are explicit, making CO₂ and R290 heat pumps less an “option” and more a “must”—aligned with natural-fluid technology roadmaps including severe-cold CO₂ cascade heating.
4. 零碳園區建設(支撐大型化戰略)
針對工業集中供熱的市場空間,政策提供了明確的園區示範路徑。
- System integration: Zero-carbon park guidance supports multi-energy complementarity and waste-heat coupling—moving from equipment sales toward park-scale integrated energy solutions, consistent with large system-integration strategies.
5. 重點行業節能降碳改造攻堅三年行動(698 號文)
In June 2026, five ministries issued the three-year energy-saving and carbon-reduction retrofit drive for nine key industries. The attached action plan lists heat pumps alongside motors, fans, pumps, and boilers as priority equipment for upgrade—moving industrial heat pumps from “encouraged” toward “retrofit inventory” status. Source: NDRC official notice (Doc. 698 and attachment). Site interpretation is for engineering orientation only—not legal advice.
- Equipment-list status: Heat pumps are explicitly named for upgrade in steel, aluminium, cement, flat glass, methanol/ammonia, and coal power—alongside motors, fans, pumps, and boilers. This aligns with the equipment-direction logic in 深度解讀 1: heat pumps are now part of industry-wide mandatory retrofit inventories, not optional add-ons.
- Typical application entry points: Steel and chemical sectors pair waste-heat recovery with heat pump upgrades; methanol/ammonia push electrification of energy systems; coal power targets heat-pump upgrades with CHP heat–power decoupling and thermal storage coupling—direct engineering openings for high-temperature and steam industrial heat pumps.
- Funding and business models: Qualifying projects may receive up to 20% central investment subsidy (benchmark-efficiency projects prioritized); tax incentives for energy-saving equipment and retrofits apply; retrofit emission reductions can serve as carbon offsets for new “two-high” projects; carbon-market quotas favor advanced performers; EMC (energy performance contracting) is explicitly encouraged—echoing the assessment and “negative-cost” logic in 深度解讀 2.
- Implementation timeline: 2026–2028 three-year drive; provincial retrofit plans and enterprise lists due by end-July 2026; enterprises in covered industries should retrofit “wherever feasible.” By end-2028, industrial sectors target a 20-percentage-point rise in capacity meeting energy-efficiency benchmarks (coal power +15 pp), with >100 Mtce savings and >200 Mt CO₂ reduction—creating a near-term project pipeline for industrial heat pump suppliers and integrators.
6. 可再生能源消費義務與綠證(42 號令)
In June 2026, four ministries jointly issued Order 42, establishing minimum renewable consumption shares and provincial renewable-electricity consumption-responsibility weights—effective 1 August 2026. For industrial heat pumps, the measure turns electrified heat supply into a compliance topic: green-power sourcing and certificate accounting matter alongside equipment efficiency. Source: NDRC Q&A on the measures (Order 42). Site interpretation is for engineering orientation only—not legal advice.
- Dual-track framework: Provincial consumption-responsibility weights (physical consumption, with green-certificate top-up if needed) plus minimum renewable consumption shares for key energy-using industries (electricity and non-electric categories)—implementing the Energy Law and translating macro dual-carbon targets into measurable obligations; aligned with the assessment logic in 深度解讀 2.
- Industrial heat pumps × green power: Heat pumps are electrified heat supply; enterprise green-power consumption shares are accounted via green certificates tied to production-year electricity—project proposals should plan PPA or certificate procurement alongside equipment selection, or “equipment savings” may not offset grid-carbon compliance pressure (see also the grey-grid vs green-power discussion on the heat pump basics page).
- Non-electric consumption and heating (cooling): Order 42 is the first framework to bring non-electric renewable use into the minimum-share system, including renewable heating (cooling); industrial waste-heat heat pumps and park-coupled heating may fit the long-term compliance narrative—but official Q&A notes that non-electric statistics and accounting systems are still maturing, with monitoring and assessment to proceed industry by industry as conditions allow.
- Coordination with Doc. 698: Steel, aluminium, cement and other industries overlap with the Doc. 698 retrofit inventory—equipment upgrade (heat pumps) + green-power consumption (Order 42) forms a combined compliance path; shortfalls may be covered via green-certificate trading within three months, with interviews, notifications and credit records for overdue non-compliance—reinforcing the “encouragement to assessment” narrative in the expert note.
7. New Energy System Construction "15th Five-Year" Plan (Doc. 884)
On 13 June 2026, NDRC and NEA issued the New Energy System Construction "15th Five-Year" Plan (Doc. 884), approved by the State Council. Chapter IV explicitly calls for green, low-carbon heat-system transition—stronger waste-heat recovery and scaled heat-pump deployment—alongside park/city heat systems, thermal storage, and flexible heat loads. Source: NEA official notice (Doc. 884). Site interpretation is for engineering orientation only—not legal advice.
- Top-level positioning: Heat-system green transition is written into the energy-sector "15th Five-Year" plan alongside the new power system and non-fossil energy scale-up. For the first time at this level, stronger waste-heat recovery and scaled heat-pump deployment appear as a paired mandate—elevating industrial heat pumps from sectoral "encouragement" to a mainstream path in energy consumption system construction.
- Industrial scenarios: waste heat + clean substitution: "Stronger waste-heat recovery" maps directly to industrial wastewater/exhaust/process heat upgraded via heat pumps to steam or hot air—aligned with high-temperature supply in 深度解讀 1 and the retrofit inventory in 深度解讀 5. "Optimised clean-substitution paths in industry" and phased reduction of captive coal plants open space to replace boilers and captive power; electrification options (electric boilers, electric kilns) are promoted for steel, petrochemical, and building-materials sectors—industrial heat pumps are the higher-efficiency electrification route. "Zero-carbon factory and park development" embeds park-scale heat pumps and waste-heat coupling as demonstration priorities (see 深度解讀 4).
- System-level upside: park heat, storage, flexibility: "Regional heat systems for cities and parks" plus integration of non-fossil heat sources with existing networks supports centralised/distributed industrial heat pumps and waste-heat sharing. Multi-scale thermal storage, flexible heat loads, CHP heat–power coordination, and joint heat–electricity–gas dispatch enable industrial steam heat pumps plus storage to participate in peak–valley balancing and green-power absorption—forming an equipment + power + storage path alongside green-power compliance in 深度解讀 6.
- 2030 targets and policy chain: By 2030: non-fossil energy share 25%, new-energy generation share 30%, and full rollout of dual carbon-control systems—raising the need for green-power/green-certificate planning in heat-pump projects. Together with the heat-pump action plan, Doc. 698, Order 42, and the energy-saving equipment program, the plan forms a top-level plan → sector program → retrofit inventory → consumption assessment chain; in external briefings, stress that industrial heat pumps sit on the main trunk of the energy consumption system, not as an isolated efficiency technology (see the expert note).
專家建議:政策邏輯要點
工業熱泵政策 · 對外溝通提示
In external briefings, stress the shift from “encouragement” to “assessment”: retrofits used to be mainly about cost; now they also respond to mandatory local carbon-intensity targets. That shift shortens industrial customer decision cycles—positioning the industry ahead of a policy-driven adoption wave.
資源列表
-
國際製冷學會 IIR 官網
成立於 1908 年的政府間組織,致力於製冷、熱泵與冷鏈領域知識與協作;提供 FRIDOC 文獻庫、出版物、國際會議及會員服務等信息。
Latest publication (Apr 2026)
IIR 發佈高溫熱泵技術簡報:工業脫碳的關鍵技術主要內容
- HTHPs (heat above 80°C) for industrial decarbonisation: ~37% of global energy use is industrial heating; 100–200°C is a core target band for food, chemical, textile, paper, and plastics processes.
- Three routes—vapor-compression, absorption, and hybrid absorption–compression—with simultaneous heating/cooling and thermal-storage integration.
- Working fluids, compressors, commercial products (about 90–300°C, kW to 100 MW), case studies, and COP >1.5 vs boilers; economics tied to electricity–fuel price ratios and grid carbon intensity.
- Policy levers: performance-based subsidies, demonstrations, carbon pricing, workforce training, and clarity on refrigerant phase-out timelines; includes a two-page Summary for Policymakers.
免費下載(IIR FRIDOC 文獻頁 — 在 Available documents 區點擊 Download)
-
IEA 熱泵技術合作項目(HPT TCP)官網
國際能源署(IEA)熱泵技術合作計劃(TCP)官方站點:工業高溫熱泵 Annex / Project 報告、供應商與示範案例數據庫、國際會議資料等。
工業高溫熱泵專題
HPT Annex 58(2020–2023)— 工業過程高溫熱泵
供熱溫度 >100°C:技術路線、系統集成、轉型策略與規格測試;2024 年發佈結題報告系列。中英 Task 1–5 導讀見下方列表首項。
Annex 58 報告與摘要
- 站內導讀 — Task 1–5(中英)
- Annex 58 出版物總覽
- Task 1 技術報告 PDF(HPT-AN58-2,直鏈)
- Task 1 技術報告(出版物頁)
- Task 2 集成方案(HPT-AN58-3)
- Task 3 應用與轉型(HPT-AN58-4)
- Task 4 規格定義與測試(HPT-AN58-5)
- 結題總報告(HPT-AN58-1)
- 執行摘要
- 2 頁摘要
HPT Project 68 / Annex 68(2024–)— 工業高溫熱泵
承接 Annex 58:滾動更新的供應商/示範數據庫、行業集成模版與 Skills4HP 培訓;Task 1 年度技術綜述已更新至 2025 版。
Project 68 資源
-
歐洲熱泵協會 EHPA 官網
歐洲熱泵協會(EHPA):歐盟熱泵政策倡導、市場情報、年度熱泵論壇與會員資源,以及工業熱泵、建築脫碳等歐盟資助項目信息。
-
Cooling Post — 全球製冷與空調產業新聞
英國製冷行業媒體,報道全球製冷、空調與熱泵產業動態、新品與技術專題。
-
ASHRAE 美國暖通空調製冷學會官網
ASHRAE 官方網站:暖通空調與製冷標準(如 Std 15、34)、手冊、研究與會議資料,以及建築系統與製冷工程相關技術資源。
-
BSRIA 英國建築服務研究與信息協會官網
英國獨立建築服務研究與諮詢機構:試驗、出版物、市場情報,以及暖通空調、熱泵與建築性能相關指南與項目信息。
最新市場情報(2026 年版 · 2025 銷售年)
Worldwide Heat Pump Markets 2026 及全球家用/商用鍋爐市場 2026 版主要結論(全球)
- 2025 sales: ~3.5 million hydronic heat pumps (+4% after a weak 2024); just under 13 million boilers sold (~90% gas). Boiler market broadly flat; transition remains gradual.
- Ratio 3.8 boilers per hydronic heat pump in 2025; ~200 million boilers in operation worldwide (~half older non-condensing units).
- ~73% of global heating demand is replacement/retrofit (>90% in mature markets)—the main competitive arena for boilers, heat pumps, hybrids, and district heating.
- Forecasts: hydronic heat pumps +8% CAGR (2019–2029); fossil fuel boilers −2% CAGR (2019–2029). By 2029, hydronic heat pumps ~12% of replacement/retrofit activity. Progressive 2035 EU scenario: ~+20% heat pump growth vs ~−7% gas boilers in top five European heating markets.
報告頁面(付費市場情報)
-
naturalrefrigerants.com
天然工質(CO₂、氨、碳氫等)行業門戶:商用製冷與暖通領域新聞、案例、法規與技術動態。
-
Dorin Selection(首頁)
意大利 Dorin 官方線上選型(Dorin Selection):機型、工況圖與應用向的壓縮機/機組數據瀏覽。
-
Bitzer WEBsoftware(中文區域)
德國 Bitzer 官網 WEBsoftware 入口(鏈接含中文區域參數):選型軟件、下載與文檔等資源彙總。
-
Bock VAP — CO₂ 跨臨界半封活塞
Bock 固定式應用在線性能數據(VAP);當前鏈接直達 CO₂ 跨臨界半封活塞壓縮機產品族(如 HG CO₂ T 系列),可在站內導航切換其他工質與排量檔。
常見問題
本頁用來做什麼?
工業熱泵相關標準、政策入口與精選外鏈的中英速查地圖——不能替代購買或引用正式標準文本。
如何查中國 / 歐盟 / 美國 / 日本標準?
在「標準」表格中定位常見 GB/T、EN、ASHRAE/AHRI、JIS 條目,再打開發布方或國家標準目錄覈對現行版本。
工業熱泵政策摘要在哪裏?
Scroll to the 政策解讀 block for national action plans, carbon-assessment notes, and natural-fluid direction pointers with source links.
這算法律或合規意見嗎?
不是。本頁僅爲工程導向說明。採購、安全、F-gas 或許可決策須以監管原文與合格顧問意見爲準。