案例庫 · 工程數據

全球工業熱能案例庫

Compare industrial cooling, heat pumps and energy recovery with your site.

Field references and public sources are labeled separately. These entries are not independently metered delivery records.

Browse industrial cooling cases ↓ · Browse energy recovery cases ↓

華中某肉類加工廠 A 的氨熱泵機組 華中某肉類加工廠 B 的氨熱泵機組

先看證據,再談效果

Two site visits, one practical starting point

See how ammonia heat pumps connect refrigeration heat to plant hot water. Site observations and reported outcomes remain distinct from independent measurements.

打開案例列表 ↓
How to read the evidence labels

兩條現場調研記錄作者所見。公開案例逐項註明投運狀態、設計值或預測的來源。

現場參考與公開來源記述保持分開。示意類條目仍處於歸檔。公開來源案例中的數字抄自所引報告或廠商說明。

先看清證據類型

三類案例明確分開

2 個案例

脫敏現場參考

作者現場觀察並隱藏客戶身份;用戶口述結果不會寫成獨立計量結論。

僅作演示

示意項目數據

用於學習操作流程,絕不描述爲客戶實測性能。

體驗演示項目 →

篩選項按已收錄案例顯示。運行狀態和證據以各案例的說明爲準。

水泥

公開來源案例

丹麥 · Aalborg Portland:水泥窯餘熱供城市熱網

餘能來源
水泥窯燃燒煙氣。
結果狀態
Cementir reports about 1 million GJ of heat delivered to Aalborg in 2023.
Key risk
供熱取決於窯線開工、熱網負荷和回水溫度。公開披露給出年度供熱量,小時和月度數據仍待覈實。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

奧爾堡水泥廠回收水泥窯煙氣餘熱,送入市政區域供熱網。

架構
水泥窯煙氣餘熱回收接入區域供熱網。
利用去向
向奧爾堡市政熱網供熱。
閱讀完整案例與來源 →

食品

公開來源案例

印度尼西亞 · Adib 勿加泗:氨/CO₂ 冷庫

供冷任務
爲凍品冷庫供冷。核證報告記錄了一臺規格製冷量爲 189 kW 的機組。
結果狀態
The JCM registry records operation from December 2014. JQA verified the project’s emissions calculation for February–July 2015.
Key risk
JCM 結果對照的是項目監測數據和方法學規定的基準。現場比較須統一庫溫和週轉量,並複覈氨系統安全及 CO₂ 迴路承壓條件。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

印尼與日本聯合碳信用機制(JCM)登記項目記錄了氨/CO₂ 製冷機組的安裝及首期監測。

架構
兩級氨製冷系統,通過獨立的 CO₂ 迴路向冷庫供冷。
閱讀完整案例與來源 →

水泥

公開來源案例

土耳其 · Çimko Narlı 水泥廠:熟料冷卻餘熱 ORC 發電

餘能來源
熟料冷卻機餘熱。
結果狀態
供應商公佈的機組設計峯值電功率爲 6.4 MWe。
Key risk
6.4 MWe 是設計峯值。來源未披露全年淨髮電量,冷卻機可用餘熱和環境溫度均會影響出力。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

Clinker cooler heat drives an air-cooled organic Rankine cycle (ORC). The supplier reports operation since June 2019.

架構
餘熱鍋爐與導熱油迴路將熟料冷卻餘熱送往 ORC。
利用去向
由空冷 ORC 機組在廠內發電。
閱讀完整案例與來源 →

油氣

公開來源案例

中國 · 國家管網海門站:天然氣餘壓發電

餘能來源
天然氣從長輸管網分輸、調壓時形成的壓差。
結果狀態
PipeChina reports operation from 19 November 2025 and projects annual generation of 3 GWh.
Key risk
The 3 GWh figure is a forecast. The cited release gives no full-year metered output. Check uninterrupted gas delivery, outlet temperature and reheating energy.

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

PipeChina reports that its Haimen gas station in Nantong started operating an expander-generator in November 2025.

架構
膨脹發電機組與原調壓系統並聯。業主披露膨脹後的天然氣採用自然通風復熱。
利用去向
發電優先自用,餘電上網。
閱讀完整案例與來源 →

食品

公開來源案例

美國 · Lineage 奧克斯納德:托盤強風速凍

供冷任務
托盤食品入庫及發運前,須達到目標品溫。
結果狀態
對單獨試用的新型速凍間,Lineage 披露其單位重量能效較原標準速凍間提高 20%,速凍速度提高 50%。
Key risk
這些是運營方披露的速凍間對比結果。估算全廠節電前,先統一產品、批量和終點中心溫度。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

Lineage 改造托盤貨物的冷風路徑,以縮短食品凍結週期並提高處理量。

架構
多風道速凍間配合高通風隔板,另試用將冷風導入各托盤的速凍間設計。
閱讀完整案例與來源 →

油氣

公開來源案例

美國 · Mary Ann 氣體處理廠:蒸汽壓差回收與調控

餘能來源
燃燒鍋爐與餘熱蒸汽發生器提供的 450 psig 高壓蒸汽。
結果狀態
The DOE case attributes 170 billion Btu per year of energy savings to the 1998 steam-system control revisions.
Key risk
披露的節能量屬於蒸汽系統控制調整,未單列發電增益。對比方案須保障下游用汽,並計入燃燒鍋爐燃料。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

美國能源部案例記錄瞭如何讓既有背壓汽輪發電機的運行跟隨下游用汽需求。

架構
既有背壓汽輪發電機與調整後的蒸汽母管控制。
利用去向
汽輪機發電,排汽供給 60 psig 中壓蒸汽母管。
閱讀完整案例與來源 →

工業製造

公開來源案例

泰國 · 索尼半導體工廠:潔淨室供冷

供冷任務
爲半導體制造維持潔淨室溫度與溼度。
結果狀態
JCM records operation starting in April 2017. The registered project covers both chilled water and compressed air.
Key risk
項目層面的減排數字包含壓縮空氣。冷凍水和壓縮空氣應分項計量,並在同等潔淨室溫溼度下比較。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

巴吞他尼府的登記項目爲新潔淨室配置變頻離心冷水機,同時建設獨立的壓縮空氣系統。

架構
變頻離心冷水機,另配獨立的多級無油空氣壓縮機。
閱讀完整案例與來源 →

鋼鐵

公開來源案例

印度 · 塔塔鋼鐵 Kalinganagar:幹熄焦餘熱發電

餘能來源
焦爐排出的紅焦,業主資料給出約 1,000°C。
結果狀態
塔塔鋼鐵於 2017 年披露已建成該設施,紅焦處理能力爲每小時 200 噸。
Key risk
200 噸/小時是紅焦處理能力。所引公告未披露全年淨髮電量。現場需覈對熄焦連續性、粉塵、氣密性和輔機耗能。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

塔塔鋼鐵披露,廠內已建成幹熄焦(CDQ)系統,回收紅焦顯熱制蒸汽並用於發電。

架構
惰性氣體冷卻紅焦,並將顯熱傳給餘熱鍋爐。
利用去向
餘熱鍋爐產蒸汽供發電。
閱讀完整案例與來源 →

食品

公開來源案例

澳大利亞 · 3 Ravens 啤酒廠:CO₂ 工藝冷卻與熱回收

供冷任務
爲啤酒生產提供工藝冷卻,有適用熱需求時回收排熱。
結果狀態
The supplier reports commissioning in June 2023 and describes the variable-duty chiller as 45 kW.
Key risk
公開效益爲綜合改造估算。驗證節能時,分別計量制冷、熱回收和光伏貢獻。

數據狀態:公開來源摘要——本站未再計量。

運行記錄與技術資料

這家墨爾本啤酒廠把 CO₂ 工藝冷卻、熱回收和儲熱接入同一項目,並同步增加光伏。

架構
可在亞臨界與跨臨界模式間切換的變負荷 CO₂ 冷水機,配合熱回收和儲熱。
閱讀完整案例與來源 →

食品

公開來源案例

新西蘭 · ANZCO 坎特伯雷肉類廠:1 MW 氨熱泵供工藝熱水

熱源溫度
未披露
熱匯溫度
未披露
Key risk
Monitoring figures come from the project team. The public summary does not detail the COP period or auxiliary loads. The 3,080 t/year in the earlier EECA note is an estimate.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

EECA records commissioning in March 2022. A project case study reports post-installation monitoring, including extra electricity use and reduced coal use.

架構
前川氨熱泵,由 Active Refrigeration 安裝。
結果狀態
The project case study reports an average COP of 4.1 after installation, with 6,356 MWh less coal energy and 4,000 MWh more electricity on the reported annual basis.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

澳大利亞 · Hardwick 肉類廠:1 MW 熱泵配合油路餘熱回收

熱源溫度
未披露
熱匯溫度
未披露
Key risk
常引用的 61% 合計兩種回收方式,適用於報告期內的工藝熱水能量。最終升至 85°C 仍需燃氣補熱。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

ARENA 資助項目的結題報告按兩個生產統計期區分熱泵供熱、油路直接熱回收和燃氣補熱。

架構
氨熱泵接入既有製冷系統,並配合油路直接熱回收和熱水儲罐。
結果狀態
For October 2023–September 2024, the final report assigns 45% of hot-water energy to the heat pump and 16% to oil heat recovery.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

荷蘭 · Kervo 果品廠:800 kW 回收製冷餘熱,供熱水並支持產汽

熱源溫度
未披露
熱匯溫度
未披露
Key risk
800 kW 爲公開的方案制熱量。單獨供汽能力、兩側溫度、整系統 COP 和年度節約未披露。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Danfoss's November 2026 case describes a Servex installation using cold-storage refrigeration heat for process hot water and steam generation.

架構
Servex 將跨臨界 CO₂ 製冷迴路與獨立的烴類工質熱泵級集成。
結果狀態
丹佛斯披露聯合方案的制熱能力爲 800 kW。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

造紙

公開來源案例

意大利 · Cartiere di Guarcino 紙廠:741 kW 低壓蒸汽熱泵級

熱源溫度
未披露
熱匯溫度
未披露
Key risk
供方 COP 5.25 屬於低壓熱泵級。6.5 bar 爲再壓縮後的設計目標,聯合系統年度性能尚無公開確認。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Cannon Bono reports operation of its heat-pump stage on cogeneration cooling heat in October 2026. The downstream MVR is a separate stage.

架構
PUSH2HEAT 電驅螺桿熱泵示範,設計在下游配置機械蒸汽再壓縮。
結果狀態
Cannon Bono 披露熱泵級制熱量 741 kW、產汽 1.2 噸/小時。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

造紙

公開來源案例

韓國 · 大邱 Ajin P&P 紙廠:108°C 熱水用於乾燥改造

熱源溫度
未披露
熱匯溫度
未披露
Key risk
1,040 RT is maximum cooling capacity. The 118°C value is a unit limit. The Project 68 steam concept does not provide annual operating results for the integrated system.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

LG reported the start of heat-pump operation in early July 2026. Project 68 separately describes the site's heat-pump and steam-recompression integration concept.

架構
電驅動無油磁懸浮壓縮熱泵。Project 68 方案另設機械蒸汽再壓縮(MVR)供汽。
結果狀態
The July 2026 supplier announcement reports operation of the hot-water heat-pump system.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

美國 · Campbell Soup 迪克森工廠:蒸汽輪機驅動機械蒸汽再壓縮

熱源溫度
未披露
熱匯溫度
未披露
Key risk
額定功率爲驅動軸功率。2013 年評估記錄的是當時裝置,現行配置及 MVR 單獨節能量待覈實。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

加州大學戴維斯分校 2013 年現場評估記錄了以蒸汽輪機驅動壓縮機、用於番茄醬蒸發濃縮的系統。

架構
蒸汽輪機以軸功驅動二次蒸汽壓縮機,構成開式機械蒸汽再壓縮熱泵。
結果狀態
評估設備表列出兩臺 MVR 壓縮機的驅動額定功率,分別爲 1,375 和 380 hp。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

油氣

公開來源案例

中國 · 吉林油田大安中轉站:燃氣發動機直驅熱泵

熱源溫度
36°C
熱匯溫度
43.78°C
Key risk
2.8 MW 含發動機餘熱,終溫仍由加熱爐補足。申報資料未給出計量期或同期燃氣和用電平衡。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

漢鍾精機 2016 年項目申報資料記載,燃氣發動機直驅壓縮機,回收油田回注水餘熱預熱摻輸水。

溫升
≈ 7.780000000000001 K
架構
燃氣發動機經變速箱和離合器帶動蒸氣壓縮式熱泵的壓縮機,系統另回收缸套水和煙氣餘熱。
結果狀態
申報方給出 2.8 MW 預熱能力,口徑爲熱泵供熱與發動機餘熱回收合計。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

工業製造

公開來源案例

日本 · 本田寄居工廠:140°C 蒸汽用於塗裝乾燥現場試驗

熱源溫度
未披露
熱匯溫度
140°C
Key risk
COP 3 來自前川守谷工廠的開發裝置試驗。本田現場 COP、年度節約及商業驗收尚無公開確認。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Mayekawa and Honda are testing a NEDO-supported steam heat pump on an automotive paint line, as reported in October 2026.

架構
前川螺桿熱泵加熱水,再通過閃蒸罐製取蒸汽。
結果狀態
Mayekawa reports field testing and preliminary findings on steam-supply function and load response by July 2026.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

越南 · Intermalt 麥芽廠:回收製冷餘熱烘乾麥芽

熱源溫度
未披露
熱匯溫度
未披露
Key risk
The CO₂ figure is an operator disclosure through the supplier. The €6.75 million order covers the wider package. Heat-pump duty, COP and stand-alone payback are undisclosed.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

在 Interflour 越南麥芽廠,氨熱泵回收發芽段製冷排熱,用於加熱烘乾空氣。

架構
GEA 氨熱泵與集中製冷系統集成。
結果狀態
GEA 案例引述業主介紹裝置已使用。麥芽廠於 2017 年啓用。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

化工

公開來源案例

英國 · 紐卡斯爾 IRD:燃氣發動機驅動產汽熱泵示範

熱源溫度
未披露
熱匯溫度
未披露
Key risk
試驗地點爲 IRD,110°C 和 600 kg/h 爲設計值。1.51 以燃料輸入爲分母,與電驅熱泵制熱 COP 的口徑不同。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

1983 年,IRD 試驗燃氣發動機驅動的產汽熱泵,並回收發動機餘熱,用於低壓工藝蒸汽。

架構
往復式燃氣發動機帶動往復式製冷劑壓縮機,發動機及煙氣餘熱用於產汽。
結果狀態
歐盟項目檔案記錄約 2,000 小時試驗。峯值制熱量 325 kW,對應燃料輸入 216 kW,一次能源利用比爲 1.51。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

Tienen 糖廠:4 MW 熱泵回收蒸發餘熱再供蒸汽

熱源溫度
75°C
熱匯溫度
138°C
Key risk
Owner quotes COP 3–5, but the later IEA HPT card still marks COP pending validation. Commissioning operation is not long-term acceptance; carbon savings are estimates.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Belgian sugar-refining installation: the November 2025 IEA HPT card records commissioning operation and subsequent compressor operation at full capacity. Annual benefits remain estimates.

溫升
≈ 63 K
架構
採用 GEA 螺桿壓縮機的閉式正戊烷熱泵,回收蒸汽熱量再製蒸汽。
結果狀態
The November 2025 IEA HPT card reports part-load commissioning followed by full compressor capacity after modifications; heating COP still awaited validation.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

Arla AKAFA 奶粉廠:高溫 CO₂ 熱泵用於噴霧乾燥

熱源溫度
未披露
熱匯溫度
未披露
Key risk
59% 降幅僅覆蓋一次風加熱用氣。GEA 的 430 kW 爲製冷量。Project 59 幻燈列 900 kW 和 COP 3.6,工況及計量邊界不足以作爲全廠性能。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

丹麥乳品廠已運行裝置及後續效果披露;本次新收錄,不是 2026 年新建項目。

架構
GEA AddCool 高溫 CO₂ 熱泵,集成供熱與製冷。
結果狀態
GEA 報告運行裝置的一次風加熱用氣下降 59%,同時提供 430 kW 有用冷量。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

喜力曼徹斯特啤酒廠:餘熱回收與熱水網絡改造

熱源溫度
未披露
熱匯溫度
90°C
Key risk
42% 是碳排強度降幅,不是能耗降幅;比較期爲半年。90°C 爲設計值,COP 與年運行小時未披露。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

New operating disclosure in September 2026; commissioned in June 2025. Public-source reference, not independently metered by this site.

架構
氨熱泵配合餘熱回收與熱水輸配管網。
結果狀態
Owner reports 33% less on-site gas and 42% lower CO₂ intensity (kg CO₂/hl), July–December 2025 versus July–December 2024.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

造紙

公開來源案例

芬蘭 delfort Tervakoski:Turboden 12 MWth 熱泵加 MVR 制工藝蒸汽

熱源溫度
8–17°C
熱匯溫度
150–180°C
Key risk
Design COP is about 2 at a very large temperature lift; the guaranteed COP itself is not published in the press note. CO₂ totals differ between the two sources.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Public sources (Turboden, 17 Feb 2026; IEA HPT demo card): a large heat pump plus mechanical vapor recompression at a delfort specialty-paper mill, reported at 12 MWth and about 20 t/h of superheated steam. Not independently metered here.

溫升
≈ 133 K
架構
閉式大型熱泵(多級離心,異丁烷)串聯機械蒸汽再壓縮,不是單獨的開式水蒸氣循環
結果狀態
Turboden announced full operation on 17 Feb 2026 and said startup COP was about 10% above the guaranteed value. The IEA card records about 2,000 test hours from July to October 2025. Vendor wording calls it the largest steam-producing heat pump built; this site does not audit that ranking.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

製藥

公開來源案例

武田維也納 AHEAD:熱泵加蒸汽壓縮機,至 11 bar(a) / 184°C

熱源溫度
70°C
熱匯溫度
184°C
Key risk
COP 4.4 對應約 120°C 的產汽熱泵級。184°C 系統邊界還包括上游供熱和下游蒸汽壓縮。約 80% 爲蒸汽相關減排的上限估計。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Public sources (SPH and the NEFI AHEAD demo card): at Takeda's Vienna pharmaceutical site, a butane heat pump and a Spilling steam compressor are reported to deliver about 2.5 t/h at 11 bar(a) / 184°C. Commissioning is given as September 2025. Not independently metered here.

溫升
≈ 114 K
架構
SPH 蒸汽熱泵先到約 115–120°C,再由 Spilling 蒸汽壓縮機提到 11 bar(a) / 184°C
結果狀態
The plant opened in September 2025. AIT confirmed monitoring had started in November 2025. Project 68’s October 2026 webinar summary describes the cascade and 184°C steam. Completed 4,000-hour results and seasonal system COP remain unpublished in the sources reviewed.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

工業製造

公開來源案例

得州 Skyven Arcturus 示範中心:1 MWth 蒸汽熱泵

熱源溫度
未披露
熱匯溫度
未披露
Key risk
新 COP 披露未同時給出熱源/蒸汽溫度對、測試時長及輔機用電邊界。產品範圍不能確定示範工況;不要把 8.0 直接與大溫升項目橫比。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Skyven reported sustained COP 8.0 at its 1 MWth Texas steam-heat-pump demonstration center on 2 September 2026, up from 6.5 at commissioning. This is a supplier disclosure; the announcement does not give the demo temperature pair or measurement boundary.

架構
Arcturus 水工質蒸汽熱泵;廠商產品說明爲真空閃蒸後多級蒸汽壓縮
結果狀態
The September 2026 announcement replaces the earlier roadmap with a supplier-reported result of 8.0. The numeric COP field remains blank because comparable test conditions are missing.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

製藥

公開來源案例

中國太極涪陵製藥廠:東方電機蒸汽熱泵至 165°C

熱源溫度
40°C
熱匯溫度
165°C
Key risk
簡訊未寫工質、蒸汽壓力和年運行小時。噸級蒸汽量不應理解成數兆瓦鍋爐替代。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Dongfang Electric (3 Feb 2026 start-up): Dongfang Electric reports an 890 kW steam heat pump and booster at the Taiji Fuling pharmaceutical plant in Chongqing, China, lifting about 40°C waste heat to 165°C saturated steam at a stated COP of 2.7. Not independently metered here.

溫升
≈ 125 K
架構
高溫蒸汽熱泵加增壓機;報道電功率約 330 kW,額定製熱 890 kW
結果狀態
Dongfang Electric’s own 3 February 2026 announcement confirms commissioning at Taiji Fuling and reports about 330 kW electrical input, 890 kW rated heat and measured COP 2.7. This is a supplier report, not this site’s independent audit.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

公開來源案例

挪威 Stella Polaris:前川氨–戊烷復疊,爲蒸煮提供蒸汽

熱源溫度
18–21°C
熱匯溫度
145°C
Key risk
2026 年申報約 700 kWth,早期案例卡爲 800 kW。設計制熱 COP 1.8 與冷熱聯合 COP 2.5 邊界不同,不能組成區間。年運行小時和實測 COP 仍未知。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

項目團隊的 2026 年 EHPA 獎項申報資料稱,芬斯納斯 Stella Polaris 已完成調試並現場產汽:約 700 kWth,18–21°C 餘熱,145°C 蒸汽。屬於項目公開披露,不是獨立現場覈驗。

溫升
≈ 124 K
架構
噴油螺桿/螺桿復疊:氨把製冷熱量抬到約 82°C,戊烷再產蒸汽
結果狀態
2026 年申報資料稱,裝置由 Stella Polaris 運行、前川遠程支持;未給出實測運行 COP 或累計小時。
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

乾燥

公開來源案例

菲利普莫里斯博洛尼亞:SPH 兩級熱泵向乾燥機供應 139°C 蒸汽

熱源溫度
36–50°C
熱匯溫度
90–139°C
Key risk
COP 2.5 is a supplier-reported FAT value. The card’s 5,000 h/year is not evidence of cumulative site runtime. Do not merge the 650 kW dryer module with PMI’s separate Crespellano heat-pump/electric-boiler program or apply owner savings percentages to the whole Bologna operation.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

SPH / JOA demo card (installation year 2025): at Philip Morris Manufacturing & Technology Bologna, a two-stage heat pump turns dryer exhaust heat into saturated steam at 139°C and 2.5 bar(g). Rated duty is 650 kW. A FAT COP of 2.5 is source-reported, not remeasured here.

溫升
≈ 40 K
架構
兩級往復式熱泵(SPH),由 JOA 與乾燥機溼排風直接熱回收集成
結果狀態
The card lists installation year 2025, about 5,000 h/a, and a COP of 2.5 measured during factory acceptance testing. That FAT figure is not a published multi-season site audit.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

工業製造

公開來源案例

湖州西塞:2 MW 空氣熱泵儲能報道滿負荷運行,蒸汽約 540°C

熱源溫度
45°C
熱匯溫度
540°C
Key risk
The April 2026 full-load account and a manufacturer retrospective of a February 2025 test give different dates and COPs. Their equipment/configuration relationship is not established here. Neither a short test nor a heat-pump COP proves annual storage-cycle performance.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Lüchu Technology (9 Apr 2026): a 2 MW-class very-high-temperature heat-pump storage demo at Xisai Science Valley, Huzhou, Zhejiang, China, reached full load. It uses air as the heat-pump fluid and molten salt as storage, and is reported to release superheated steam near 540°C at a COP of 1.41 from about 45°C waste heat. Not a process-steam heat pump, and not independently metered here.

溫升
≈ 495 K
架構
空氣熱泵給熔鹽充熱,再釋放高溫蒸汽——熱泵儲能,不是閉式產汽再串機械蒸汽再壓縮
結果狀態
The builders reported full-load operation on 9 Apr 2026. Electric input is about 1.5 MW and heating output about 2 MW. COP 1.41 is source-reported for the 45°C source. A separate 8 MW / 400°C phase was announced earlier and is not treated here as this operating unit.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

工業製造

公開來源案例

上海電氣奉賢:1.1 MW 熔鹽儲熱耦合高溫熱泵供汽

熱源溫度
未披露
熱匯溫度
未披露
Key risk
高於 100% 的綜合效率是覈算口徑,不是蒸氣壓縮 COP。不要把本條歸入工藝蒸汽熱泵。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Shanghai Electric (acceptance 9 May 2025): a 1.1 MW / 10.8 MWh molten-salt store coupled to a high-temperature heat pump, supplying industrial steam at a factory in Fengxian, Shanghai. This is thermal storage plus a heat pump, not a process-steam heat pump of the closed-cycle plus MVR type. Not independently metered here.

架構
單罐熔鹽儲熱耦合高溫熱泵,用於綠色供汽
結果狀態
Shanghai Electric reported that after more than two months of trial operation the system passed the owner's acceptance on 9 May 2025 and entered commercial operation. Steam conditions are not published as one fixed pair.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

化工

公開來源案例 在建

巴斯夫路德維希港:CompriVAP 開式熱泵,最多約 50 MW 工藝蒸汽,尚未投運

熱源溫度
未披露
熱匯溫度
未披露
Key risk
Under construction. Capacity, up to 500,000 tonnes/year of steam and up to 100,000 tonnes/year of avoided CO₂ are project targets. The team quotes a design COP of up to 3.4. Operating COP and annual outcomes are unconfirmed.

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Public project note: BASF has started construction at Ludwigshafen, Germany, of an open heat-pump system (GKT CompriVAP, formerly GIG Karasek) meant to turn steam-cracker waste heat into up to 50 MW of process steam. Commissioning is scheduled for mid-2027. This entry is under construction, not an operating case.

架構
開式 CompriVAP 熱泵——與 delfort 紙廠的閉式熱泵串聯機械蒸汽再壓縮不是同一條路線
結果狀態
GKT reported on 3 September 2026 that the first compressors had been positioned and the evaporator stage, vessels, pumps and heat exchangers installed. Piping and electrical work continued. BASF’s commissioning target remains mid-2027.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

區域供熱

公開來源案例 在建

維西尼蒂 Kendall(劍橋):35 MW 河水源熱泵制區域蒸汽,安裝目標 2028 年

熱源溫度
未披露
熱匯溫度
未披露
Key risk
35 MW 爲計劃容量。2026 年說明寫的是預熱用途,不能據此確定熱泵直接產汽量或實測 COP。必須區分已運行電鍋爐與未來熱泵。

Public reports, papers, or vendor materials — source and assumptions labeled

運行記錄與技術資料

Vicinity’s May 2026 update keeps its 35 MW Charles River heat-pump complex at Kendall on a 2028 installation target. The stated role is to preheat water for an electric boiler supplying district steam. It remains an engineering/construction project, not an operating heat-pump case.

架構
River-source heat recovery to preheat water for the district-steam electric boiler, per the May 2026 owner account
結果狀態
The 11 May 2026 owner update says heat-pump engineering is active and installation is planned by 2028. Kendall’s electric boiler entered service in November 2024; its eSteam supply is not evidence that the heat pump is operating.
數據來源
Public reports, papers, or vendor materials — source and assumptions labeled
匿名化
名稱來自公開來源
閱讀完整案例與來源 →

食品

脫敏現場參考

華中肉類加工廠 A:氨熱泵回收製冷排熱製取廠區熱水

熱源溫度
28–35°C
熱匯溫度
55–75°C
Key risk
調研油品首年須更換;管路清潔度;後續宜將預熱器與冷凝蒸發器撬裝化

Anonymized engineering notes — field observations and reported outcomes, not independent metering

運行記錄與技術資料

作者現場調研(2024-05):氨中溫熱泵經預熱器+冷凝蒸發器與廠區氨製冷耦合;用戶口述日製熱水約 400–500 m³,替代外購蒸汽。

溫升
≈ 20 K
架構
氨中溫熱泵,經預熱器+冷凝蒸發器+輔助貯液器下液路徑與在運製冷耦合
結果狀態
May 2024 survey record: Overall operation reported as good; steam purchase displaced for a large share of plant hot-water duty
數據來源
Anonymized engineering notes — field observations and reported outcomes, not independent metering
匿名化
已省略客戶名
閱讀完整案例與來源 →

食品

脫敏現場參考

華中肉類加工廠 B:氨熱泵制熱水——耦合與運維經驗

熱源溫度
28–35°C
熱匯溫度
50–70°C
Key risk
首年換油;軸封泄漏監測;安裝清潔度(過濾器雜質);客戶建議的排氣總管顯熱換熱器(氨氣 80→65℃、免費抬溫)屬未覈驗建議

Anonymized engineering notes — field observations and reported outcomes, not independent metering

運行記錄與技術資料

Author field survey (2024-05): same ammonia HP architecture as plant A at a second Central China meat site; plant-reported ~200–300 m³/day hot water and ~¥100k/month steam savings, plus liquid-path and cleanliness lessons.

溫升
≈ 15 K
架構
氨中溫熱泵;下液宜進輔助貯液器(冬季油冷供液),不宜僅接主貯液器
結果狀態
May 2024 survey record: Overall operation reported as good; plant continues to displace purchased steam for hot water
數據來源
Anonymized engineering notes — field observations and reported outcomes, not independent metering
匿名化
已省略客戶名
閱讀完整案例與來源 →