新西蘭 · ANZCO 坎特伯雷肉類廠:1 MW 氨熱泵供工藝熱水
EECA records commissioning in March 2022. A project case study reports post-installation monitoring, including extra electricity use and reduced coal use.
Run detailed calculation with this case一键代入详细计算
工程數據
- 案例類型
- 公開來源案例 — 數據來自公開報告、論文或廠商資料
- 數據狀態
- 公開來源案例
- 數據來源
- EECA installation and original estimate: https://www.eeca.govt.nz/insights/eeca-insights/industrial-heat-pumps-for-process-heat/ — RACE for 2030 / DETA, updated case study: https://www.racefor2030.com.au/content/uploads/ANZCO-Foods-Canterbury-heat-pump-case-study-final.pdf
- 審閱 / 日期
- Editorial (Open Thermal AI) · 2026-11-21
- 行業
- 食品
- 熱源溫度
- 未披露
- 熱匯溫度
- 未披露
- 溫升
- 不適用
- 供熱/製冷負荷
- 1000 kW
- 架構
- 前川氨熱泵,由 Active Refrigeration 安裝。
- 結果狀態
- The project case study reports an average COP of 4.1 after installation, with 6,356 MWh less coal energy and 4,000 MWh more electricity on the reported annual basis.
- Key risk
- Monitoring figures come from the project team. The public summary does not detail the COP period or auxiliary loads. The 3,080 t/year in the earlier EECA note is an estimate.
- 原有系統
- 兩臺燃煤鍋爐供汽並間接制熱水;熱水環網與就地電補熱服務各加工區。
- 製冷劑
- R717
- COP
- 未披露
- 年度節能 / 減排
- The case study reports 2,356 MWh/year net energy savings and an 8% site emissions reduction (1,750 t CO₂e).
- 預計回收期
- 所覈對來源未披露。
項目背景
EECA 記錄新西蘭阿什伯頓 1 MW 裝置。後續 RACE for 2030 案例研究說明 DETA 開展了投運後的監測驗證。
敘述性輸入
取得同期製冷與熱水負荷、環網回水溫度和各區域補熱要求。
熱泵方案
回收製冷餘熱供熱水管網,同時保留補熱以滿足溫度和負荷要求。
COP 與節能
保留案例研究披露的平均 COP 4.1 及監測語境。借鑑前應確認計量邊界、氨安全措施及備用熱源用量。
投資回報要點
本條未確定熱泵單獨回收期。請按自身計量負荷、能源價格、集成投入及備用供熱單獨估算。