武田維也納 AHEAD:熱泵加蒸汽壓縮機,至 11 bar(a) / 184°C
Public sources (SPH and the NEFI AHEAD demo card): at Takeda's Vienna pharmaceutical site, a butane heat pump and a Spilling steam compressor are reported to deliver about 2.5 t/h at 11 bar(a) / 184°C. Commissioning is given as September 2025. Not independently metered here.
Run detailed calculation with this case一键代入详细计算
工程數據
- 案例類型
- 公開來源案例 — 數據來自公開報告、論文或廠商資料
- 數據狀態
- 公開來源案例
- 數據來源
- SPH project note: https://spheat.de/blog-en/takeda-relies-on-industrial-heat-pumps-for-steam-generation-in-the-ahead-project?lang=en — NEFI AHEAD demo card: https://spheat.de/neu/wp-content/uploads/2026/03/demo26ahead20251008.pdf — AIT, 28 Nov 2025: https://presse.ait.ac.at/news-ait-and-takeda-win-the-deca-award-2025-industry-for-the-nefi-project-ahead?id=227830&l=english&menueid=34059 — IEA HPT Project 68 webinar summary, 2 Oct 2026: https://heatpumpingtechnologies.org/project68/successful-webinar-high-temperature-heat-pumps-in-the-bio-pharmaceutical-industry/
- 審閱 / 日期
- Editorial (Open Thermal AI) · 2026-11-21
- 行業
- 製藥
- 熱源溫度
- 70°C
- 熱匯溫度
- 184°C
- 溫升
- ≈ 114 K
- 供熱/製冷負荷
- 1700 kW
- 架構
- SPH 蒸汽熱泵先到約 115–120°C,再由 Spilling 蒸汽壓縮機提到 11 bar(a) / 184°C
- 結果狀態
- The plant opened in September 2025. AIT confirmed monitoring had started in November 2025. Project 68’s October 2026 webinar summary describes the cascade and 184°C steam. Completed 4,000-hour results and seasonal system COP remain unpublished in the sources reviewed.
- Key risk
- COP 4.4 對應約 120°C 的產汽熱泵級。184°C 系統邊界還包括上游供熱和下游蒸汽壓縮。約 80% 爲蒸汽相關減排的上限估計。
- 原有系統
- 製藥生產與滅菌原用天然氣蒸汽;現場製冷或既有熱水熱泵可提供餘熱
- 製冷劑
- R717 (upstream heat pump) / R600 (steam-generating heat pump) / R718 (steam compressor)
- COP
- 未披露
- 年度節能 / 減排
- The project cites potential reductions of up to about 1,600 t/year CO₂ and up to about 80% of steam-related emissions under its stated conditions. The October 2026 webinar summary repeats the upper percentage without a completed annual metering result.
- 預計回收期
- 所用來源未披露回收期
項目背景
AHEAD(先進熱泵示範)是武田維也納製藥廠區的點名裝置,參與方包括 AIT 與 SPH,資金來自奧地利 NEFI 計劃。這是公開來源的工藝蒸汽案例,與本站匿名現場調研分開。
敘述性輸入
熱源:約 70°C 熱水。熱匯:11 bar(a) / 184°C 蒸汽,來源所寫熱泵額定製熱約 1.7 MW、蒸汽約 2.5 t/h。第一級用正丁烷,第二級壓縮水蒸氣。
熱泵方案
SPH 熱泵把熱水熱源做成接近 115–120°C 的蒸汽(SPH 一處描述約 1.9 bar(a))。Spilling 蒸汽壓縮機再將蒸汽提到約 11 bar(a)、184°C,供製藥用途。
COP 與節能
Reported COP about 4.4 belongs to the heat-pump stage producing steam near 120°C at up to 1.7 MW. The downstream compressor delivers about 2.5 t/h at 184°C. Up to 1,600 tonnes/year of CO₂ savings is a potential benefit. AIT confirms monitoring is underway, without publishing a completed annual performance result in the source reviewed.
投資回報要點
所用來源沒有投資與回收期。減排數字保持爲項目方陳述。
FAQ
這是獨立計量覈驗案例嗎?
不是。證據等級爲公開來源。見 SPH 項目說明與 NEFI AHEAD 案例卡(文件日期 2025-10-08)。本站未對維也納工廠計量。
爲什麼卡片上不寫 COP?
公開的約 4.4 COP 屬於約 120°C 蒸汽的熱泵級。184°C 工藝蒸汽還經過第二級壓縮,卡片上若只寫一個 COP,會把兩個邊界混在一起。