Takeda Vienna AHEAD: heat pump plus steam compressor to 11 bar(a) / 184°C
Public sources (SPH and the NEFI AHEAD demo card): at Takeda's Vienna pharmaceutical site, a butane heat pump and a Spilling steam compressor are reported to deliver about 2.5 t/h at 11 bar(a) / 184°C. Commissioning is given as September 2025. Not independently metered here.
Jalankan perhitungan rinci dengan kasus ini一键代入详细计算
Data teknik
- Jenis kasus
- Kasus sumber publik - angka dari laporan yang diterbitkan, makalah, atau bahan vendor
- Status data
- Kasus sumber publik
- Sumber data
- Catatan proyek SPH: https://spheat.de/blog-en/takeda-relies-on-industrial-heat-pumps-for-steam-generation-in-the-ahead-project?lang=en - Kartu demo NEFI AHEAD: https://spheat.de/neu/wp-content/uploads/2026/03/demo26ahead20251008.pdf - AIT, 28 Nov 2025: https://presse.ait.ac.at/news-ait-and-takeda-win-the-deca-award-2025-industry-for-the-nefi-project-ahead?id=227830&l=english&menueid=34059 — IEA HPT Project 68 webinar summary, 2 Oct 2026: https://heatpumpingtechnologies.org/project68/successful-webinar-high-temperature-heat-pumps-in-the-bio-pharmaceutical-industry/
- Peninjau / tanggal
- Editorial (Open Thermal AI) · 2026 -11 -21
- Industri
- Farmasi
- Suhu sumber
- 70°C
- Suhu waseng
- 184°C
- Angkat suhu
- ≈ 114 K
- Pemanasan atau tugas pendinginan
- 1700 kW
- Arsitektur
- Pompa panas penghasil uap SPH hingga sekitar 115 – 120 °C, kemudian kompresor uap Spilling hingga 11 bar (a) / 184 °C
- Status hasil
- The plant opened in September 2025. AIT confirmed monitoring had started in November 2025. Project 68’s October 2026 webinar summary describes the cascade and 184°C steam. Completed 4,000-hour results and seasonal system COP remain unpublished in the sources reviewed.
- Risiko utama
- COP 4.4 applies to the steam-generating heat-pump stage around 120°C. The 184°C boundary also needs upstream heat supply and downstream steam compression. The cited 80% is an upper estimate for steam-related emissions.
- Sistem yang ada
- Uap gas alam untuk produksi farmasi dan sterilisasi; limbah panas yang tersedia dari pendingin situs / pompa panas air panas yang ada
- Refrigeran
- R717 (pompa panas hulu) / R600 (pompa panas penghasil uap) / R718 (kompresor uap)
- COP
- Tidak diungkapkan
- Penghematan energi / emisi tahunan
- The project cites potential reductions of up to about 1,600 t/year CO₂ and up to about 80% of steam-related emissions under its stated conditions. The October 2026 webinar summary repeats the upper percentage without a completed annual metering result.
- Perkiraan pengembalian
- Tidak diungkapkan dalam sumber yang digunakan di sini
Latar belakang proyek
Proyek AHEAD (Advanced Heat Pump Demonstrator) adalah instalasi bernama di kampus farmasi Takeda di Wina, dengan AIT dan SPH, didanai di bawah program NEFI Austria. Ini adalah kasus ruang-steam proses sumber publik, terpisah dari survei lapangan anonim situs ini.
Input Narasi
Source: about 70°C hot water. Sink: steam at 11 bar(a) / 184°C, about 2.5 t/h and 1.7 MW thermal as reported for the heat-pump rating. The first stage uses n-butane; the second stage compresses steam.
Solusi pompa panas
The SPH heat pump turns the hot-water source into steam near 115–120°C (about 1.9 bar(a) in one SPH description). A Spilling steam compressor then raises that steam to about 11 bar(a) and 184°C for pharmaceutical duties.
COP & tabungan
Reported COP about 4.4 belongs to the heat-pump stage producing steam near 120°C at up to 1.7 MW. The downstream compressor delivers about 2.5 t/h at 184°C. Up to 1,600 tonnes/year of CO₂ savings is a potential benefit. AIT confirms monitoring is underway, without publishing a completed annual performance result in the source reviewed.
Catatan investasi / ROI
Biaya modal dan pengembalian tidak ada dalam sumber yang digunakan di sini. Klaim emisi tetap diberi label sebagai pernyataan proyek.
FAQ
Apakah ini proyek terukur yang terverifikasi?
Tidak. Tingkat bukti adalah sumber publik. Lihat catatan proyek SPH dan kartu demo NEFI AHEAD (tanggal file 2025 -10 -08). Situs ini tidak mempaikan pabrik Wina.
Mengapa COP dibiarkan kosong di kartu?
The published COP near 4.4 belongs to the heat-pump stage at about 120°C steam. The process steam at 184°C includes a second compression stage, so a single card COP would mix two different boundaries.