現場準備單

製冷餘熱回收準備單

選定一臺設備或一道工序,按項記錄。未掌握的數據留空,資料和原理在下方繼續閱讀。

電子填寫需要啓用 JavaScript。以下空白單仍可通過瀏覽器打印,原指南繼續保留。

打印空白單

Open Thermal AI · Blank sheet

製冷餘熱回收準備單

Sheet ID: ________________ · Template version: 2026-10-18.1

工廠/車間
 
設備名稱或編號 / 工序名稱
 
記錄人
 
調查日期
 

專項清單以氨系統爲例。其他製冷劑僅作通用記錄,須單獨專業覈查。只查現有資料;接表、開管、取樣或調整設定須由合格人員按現場程序執行。

已記錄不等於已覈實。填寫完成不代表安全合格、項目可行或節能收益;專業人員仍需複覈。

RF-01 · Confirm the refrigeration system and fluid · ________
系統位號、製冷劑、級數、設備及原製冷用途
Where to look; what to do if missing: Use drawings, labels and the responsible person; confirm an unknown fluid first.
設備編號(位號)通常在現場標籤或圖紙上。沒有編號時先寫設備名稱和位置,並註明編號待確認,不必編造正式編號。
製冷劑 
級數和原製冷用途 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-02 · Read suction and discharge records · ________
Suction/discharge temperatures, pressures and bases, and load state.
Where to look; what to do if missing: Read existing controls and logs; no gauge installation or pipe opening is requested.
Suction temperature (°C) 
Discharge temperature (°C) 
吸排氣壓力及單位/基準 
負荷狀態 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-03 · Record condensing conditions separately · ________
冷凝壓力/溫度、散熱方式、日期和環境條件
Where to look; what to do if missing: Use existing trends; discharge temperature is not a constant heat-source temperature.
冷凝壓力及單位/基準 
Condensing temperature (°C) 
散熱方式和環境條件 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-04 · Check same-period electricity · ________
Actual compressor power or energy and period, including auxiliary scope.
Where to look; what to do if missing: Use meters/controls; rated power is not actual electricity use.
實際功率或電量及單位 
對應時間與輔助設備範圍 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-05 · Check the existing recovery loop · ________
Fluid, inlet/outlet temperatures, actual flow and current use.
Where to look; what to do if missing: Use diagrams and trends; distinguish desuperheat from condensation.
回收介質和用途 
Loop inlet temperature (°C) 
Loop outlet temperature (°C) 
實際流量及單位 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-06 · Record simultaneous heat demand · ________
用途、溫度、流量、熱源/用熱重疊時間
Where to look; what to do if missing: Use the hot-water sheet and the same recording period.
Overlap hours are the times when source heat is available and the process needs heat simultaneously. Compare both operating logs. Do not assume 8,760 hours or use only one side’s running hours. Storage for mismatched timing needs separate assessment.
用熱用途及相關準備單編號 
Supply/return temperatures (°C) 
實際流量及單位 
同時運行時段 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-07 · Review constraints and outstanding actions · ________
壓力/油管理/水質/隔離等現有記錄,負責人員
Where to look; what to do if missing: Use maintenance/safety records; unconfirmed conditions need professional review.
未處理事項和限制 
專業複覈人及資料編號 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 
RF-08 · Check control priority and seasons · ________
製冷優先要求、備用供熱、季節運行記錄
Where to look; what to do if missing: Use process/control documents; do not raise condensing pressure to create apparent savings.
製冷優先和備用供熱 
季節運行記錄 
記錄狀態□ Not reviewed □ Recorded □ Needs measurement □ Needs confirmation □ Not applicable (explain)
資料類型 
資料編號/來源說明 
測點/對象位置 
記錄時間或起止週期 
運行狀態(生產/清洗/待機等) 
備註/關聯準備單編號 
待辦負責人 
約定完成日期 
不適用的原因 
複覈人、日期與意見(由人填寫) 

Guide source: https://www.openthermalai.com/en/insights/ammonia-refrigeration-heat-recovery-screening.html

保存在本瀏覽器,不自動上傳。清理瀏覽器數據或更換設備前請導出備份;不提供雲端同步或完整離線保證。

已記錄不等於已覈實。填寫完成不代表安全合格、項目可行或節能收益;專業人員仍需複覈。

Field rule: recoverable heat is not the same as useful heat. Measure the refrigeration boundary and the simultaneous hot-water or process demand before choosing desuperheating, condenser recovery or a booster heat pump.

氨製冷餘熱能否提供有用的熱水?

It can be a candidate when source temperature, available heat and hot-water demand overlap. First separate discharge desuperheating from condensation, then measure temperatures, flow, compressor electricity and demand on a common time base. Compare direct recovery before selecting a booster heat pump.

Protect refrigeration duty and ammonia-system safety. Missing measurements mean more data is needed, not that the project is viable. The checklist below supports screening; it is not a design or operating instruction.

氨製冷系統的熱量在哪裏

Compressor discharge is not one constant-temperature source. Split it before treating it as recoverable heat:

  • Desuperheat: a smaller share, at a higher temperature.
  • Condensation: the larger duty, at a lower temperature.
  • Liquid subcooling: a further portion that may remain after condensation.

Refrigeration operation, compressor staging, ambient conditions and product load move the available temperature and duty. Use operating distributions, not one summer design point.

現場測量清單

BoundaryMeasure or verifyWhy it matters
製冷類Suction and discharge pressure and temperature; condensing pressure and temperature; each compressor power and loadAvailable heat, and whether recovery adds power
Recovery loopInlet and outlet temperature of water or the secondary fluid; calibrated flow; pump powerUseful recovered heat
Heat demandSupply and return temperature; hourly flow; production schedule; hygiene boundaryDemand that is both useful and simultaneous
基準方案Boiler fuel, steam or electric heating over the same periodA saving comparison on the same hours
ConditionOil carried in the discharge; water quality; fouling and corrosion; relief and isolationReliability and safety

Make the data reusable: record the time period, unit, measurement point, operating condition and source for each value. Mark whether it is measured, taken from a bill or drawing, or assumed. Leave unknown values blank and name the next measurement needed; do not treat a case-study value as your site measurement.

Already have temperatures and energy prices? First confirm the original refrigeration duty, safety constraints and whether direct heat exchange can serve the load. If an electrically driven heat pump is needed to raise temperature, compare energy costs per kWh of useful heat. This is a cost estimate, not an ammonia-system retrofit or safety design. Costs may increase or decrease; it excludes linked benefits in the refrigeration system and cannot establish annual benefits without heat quantity and overlapping hours. Keep unknown inputs pending verification.

測量後再選擇架構

After the measurements, test routes in this order:

  1. Desuperheater preheat: only a limited high-temperature duty. The high-grade share changes with discharge condition.
  2. Condenser recovery at normal head pressure: more heat, at a lower temperature. Do not raise condensing pressure for recovery unless a whole-system calculation shows a net benefit.
  3. Booster heat pump: only if the temperature is still short. It needs its own source and sink boundary, auxiliaries and safety boundary, and the low-temperature recovery loop itself must be stable.

Two add-ons, not separate heat sources:

  • Secondary loop: add it when product hygiene, water quality or the ammonia charge makes a direct arrangement unsuitable.
  • Buffer storage: it can cover a short timing gap. It cannot fix a large seasonal mismatch.

初篩風險臺賬至少應包括這些事項

  • Ammonia safety: toxicity, leak detection, ventilation, emergency isolation and site procedures.
  • Pressure equipment: classification, relief discharge and the local code that applies.
  • Effect on refrigeration: higher head pressure, discharge temperature, oil management and loss of capacity.
  • Cross-contamination: barriers for food, potable water or a clean process.
  • Water and access: fouling, water treatment, cleanability, and whether maintenance forces an unacceptable shutdown.
  • Control priority: which side is protected when refrigeration demand and heat demand move in opposite directions.
  • After handover: who owns operation, alarms, maintenance and performance checks.

實用的繼續/暫緩判斷

  • Advance when representative data shows stable recoverable heat, simultaneous demand, an acceptable temperature route, and a net system saving that does not compromise refrigeration duty or safety.
  • Advance with conditions when the route looks plausible, but flow, overlap, the head-pressure effect or integration cost still needs measurement.
  • 暫停 when the case depends on unmeasured waste heat, permanently higher head pressure, an unresolved ammonia safety boundary, or heat demand at a different time from refrigeration.

Missing information? Return to the field preparation sheet, keep unknowns explicit and print pending actions. The sheet does not automatically populate screening inputs.

Have source, demand, timing and price data? Start screening with your own inputs and sources →. You can also compare an anonymized field reference and its limits; its values do not establish your project’s performance.

安全與工程邊界

Ammonia systems require qualified refrigeration and pressure-equipment professionals. This checklist is not a hazard analysis, code determination, process-safety review, control sequence or construction design. Do not change setpoints, relief systems, piping or isolation arrangements based on this page.

依據與使用方式

This is an editorial engineering decision guide, not a measured project outcome. Calculated examples and assumptions are identified in the text. Field references retain their own evidence labels; plant-reported results are not independently verified savings.

For the site evidence, read anonymous plant A and plant B. Use the standards directory to reach primary publications, and confirm their applicability with the responsible engineer. See our editorial and source principles.