デルフォート・テルヴァコスキ(フィンランド):ターボデン 12 MWth ヒートポンプ +プロセス蒸気用MVR
Public sources (Turboden, 17 Feb 2026; IEA HPT demo card): a large heat pump plus mechanical vapor recompression at a delfort specialty-paper mill, reported at 12 MWth and about 20 t/h of superheated steam. Not independently metered here.
エンジニアリングデータ
- ケースタイプ
- 公開情報データ — 公開された報告書、論文、または販売業者資料の数値
- データ状態
- パブリックソース事件
- データソース
- Turboden press release, 17 Feb 2026: https://www.turboden.com/company/media/press/press-releases/4947/turboden-successfully-starts-up-the-worlds-largest-steam-producing-heat-pump-setting-a-new-benchmark-for-industrial-decarbonization — IEA HPT デモカード: https://heatpumpingtechnologies.org/content/uploads/sites/81/2026/01/demo35turbodenpapermill20251013.pdf — Owner, 18 Feb 2026: https://delfortgroup.com/wp-content/uploads/2026/02/delfort-is-converting-the-first-paper-prodution-site-to-run-entirely-on-fossile-free-energy.pdf?v=1771400275 — ターボデン英語ケースページ: https://www.turboden.com/case-histories/5278/delfortgroup — ターボデン・イタリアンのケースページ: https://www.turboden.com/it/case-history/5278/delfortgroup
- レビュアー/日付
- Editorial (Open Thermal AI) · 2026-11-02
- 産業
- パルプおよび紙
- ソース温度
- 8–17°C
- シンク温度
- 150–180°C
- 温度上昇
- ≈ 133 K
- 暖房または冷却の義務
- 12000kW
- 建築
- MVRとの直列で閉じた大型ヒートポンプ(多段式遠心式、イソブタン)は、オープンウォーター・ベイポームサイクルだけではない
- 結果の状態
- Turboden announced full operation on 17 Feb 2026 and said startup COP was about 10% above the guaranteed value. The IEA card records about 2,000 test hours from July to October 2025. Vendor wording calls it the largest steam-producing heat pump built; this site does not audit that ranking.
- 重要なリスク
- Design COP is about 2 at a very large temperature lift; the guaranteed COP itself is not published in the press note. CO₂ totals differ between the two sources.
- 既存のシステム
- 特殊紙製造用化石燃料焚き蒸気。低品位のプロセスによる廃棄物処理が現場で利用可能
- 冷媒
- イソブタン(IEA HPTデモカード);スチームサイドは機械式蒸気再圧縮です
- COP
- 2
- 年間エネルギー/排出量削減
- Two public figures, not reconciled here: Turboden cites about 19,000 t/a CO₂ avoided (calculated Scope 1); the IEA card cites about 15,000 t/a
- 推定返済額
- ここで使用されている情報源には明かされていません
プロジェクトの背景
The owner’s 18 February 2026 announcement identifies Tervakoski, Finland, as the mill and confirms commissioning of a heat pump and electrode boiler. The heat-pump/MVR package recovers paper-process waste heat for steam.
物語の入力
Heat source: process waste heat reported near 10–20°C. Heat sink: superheated steam reported at 3.4 bar(a), 150–180°C, about 12 MWth and about 20 t/h. Working fluid on the heat-pump side: isobutane, per the IEA HPT demo card.
ヒートポンプ溶液
A closed isobutane heat pump lifts low-grade heat; MVR then brings the steam to the pressure the paper process already uses. Turboden describes the two machines as coordinated across operating phases, inside an existing room with limited footprint.
COP&貯蓄
IEA HPT demo card: design COP about 2, installation year 2025, about 2,000 test hours (July–October 2025), estimated CO₂ savings about 15,000 t/a. Turboden press release (17 Feb 2026): unit fully operational, startup COP about 10% above the guaranteed value, calculated Scope 1 avoidance about 19,000 t/a. This site has not remeasured either figure.
Investment / ROI notes
The owner reports over €50 million for the site’s energy transformation, including an electrode boiler. This is not the heat-pump purchase price; standalone heat-pump investment and payback remain undisclosed.
FAQ
これは検証済みの測定済みプロジェクトですか?
No. Evidence level is public-source. Figures come from Turboden's 17 Feb 2026 press release and the IEA HPT demo card (demo35, dated in the file name 2025-10-13). This site did not meter the plant.
このサイトの肉植物のケースとこれはどのように異なりますか?
Those two entries are anonymized author field surveys of ammonia heat pumps making hot water. This entry is a named public steam project: a closed heat pump plus MVR, with vendor and IEA figures left side by side where they differ.
What changed in the 2 November 2026 review?
Added the owner-confirmed mill location and investment boundary. Turboden’s English case page says January 2026 operation; its Italian page says February. Retain the February commissioning announcements without choosing an exact month from inconsistent versions. No newer annual measured COP was located.