UK · IRD Newcastle: gas-engine-driven steam heat pump demonstrator
A 1983 demonstration tested a gas-engine-driven heat pump with engine heat recovery for low-pressure process steam.
Run detailed calculation with this case一键代入详细计算
Engineering data
- Case type
- Public-source case — figures from published reports, papers, or vendor materials
- Data status
- Public-source case
- Data source
- European Commission CORDIS demonstration record: https://cordis.europa.eu/project/id/EE.-00146-81 — IRD prototype final report summary, EUR 6262: https://aei.pitt.edu/35354/1/A1711.pdf
- Reviewer / date
- Editorial (Open Thermal AI) · 2026-11-21
- Industry
- Chemical
- Source temperature
- Not disclosed
- Sink temperature
- Not disclosed
- Temperature lift
- Not applicable
- Heating or cooling duty
- Not disclosed
- Architecture
- A reciprocating gas engine drives the reciprocating refrigerant compressor. Heat from the engine and its exhaust is recovered for steam duty.
- Result status
- The EU project summary reports 2,000 trial hours, with peak heat output of 325 kW at 216 kW fuel input and a primary-energy ratio of 1.51.
- Key risk
- The trial took place at IRD, and the 110°C and 600 kg/h figures describe the design. The reported ratio 1.51 uses fuel input and differs in scope from an electric heating COP.
- Existing system
- The project targeted chemical-industry steam duty. The unit was installed at IRD and tested under conditions similar to those of the intended industrial process.
- Refrigerant
- R-114
- COP
- Not disclosed
- Annual energy / emissions savings
- Not established in the sources reviewed.
- Estimated payback
- Not established in the sources reviewed.
Project background
The European Commission project archive records commissioning at IRD in January 1983. An earlier plan proposed using exhaust heat at a chemical plant.
Narrative inputs
For a new application, check required steam pressure and flow, water quality, coincident waste heat and steam demand, and the fuel heating-value basis.
Heat pump solution
Use the gas engine’s shaft output to run the compressor. Steam generation uses condenser heat and recovered engine heat.
COP & savings
Treat 325 kW and 216 kW as reported trial-point figures. The 2,000 hours are accumulated trials. Annual performance would require fuel, auxiliary power and delivered steam logs.
Investment / ROI notes
CORDIS reports a historical estimate of 3.6–4.9 years. A new estimate needs current prices, installed cost, maintenance and backup steam.