Stella Polaris, Norway: Mayekawa ammonia–pentane cascade for cooker steam

The project team’s 2026 EHPA award submission reports successful commissioning and on-site steam production at Stella Polaris, Finnsnes: about 700 kWth, waste heat at 18–21°C and steam at 145°C. Public project disclosure, not independent field verification.

Run detailed calculation with this case

Engineering data

Case type
Public-source case — figures from published reports, papers, or vendor materials
Data status
Public-source case
Reviewer / date
Editorial (Open Thermal AI) · 2026-11-02
Industry
Food
Source temperature
18–21°C
Sink temperature
145°C
Temperature lift
≈ 124 K
Heating or cooling duty
700 kW
Architecture
Oil-lubricated screw/screw cascade: ammonia lifts refrigeration heat to about 82°C, pentane then produces steam
Result status
The 2026 submission says the plant is operated by Stella Polaris with remote support from Mayekawa. No measured operating COP or cumulative hours are given.
Key risk
The 2026 submission gives about 700 kWth, whereas the earlier card gives 800 kW. Heating design COP 1.8 and combined heating/cooling COP 2.5 have different boundaries and are not a range. Annual hours and measured COP remain unknown.
Existing system
Propane-fired steam boiler for shrimp cooking; refrigeration plant rejecting heat near 18°C
Refrigerant
Ammonia (bottom) and pentane (top)
COP
Not disclosed
Annual energy / emissions savings
IEA card: estimated about 621 t/a CO₂ versus the propane boiler; investment listed as €0.8 million excluding integration
Estimated payback
Not stated as a verified payback in the card used here

Project background

Stella Polaris in Finnsnes, Norway, cooks and peels cold-water shrimp. The EU SPIRIT project and Mayekawa published a cascade heat pump that replaces the propane steam boiler for the cooker. This is a public food-industry steam case, distinct from this site's anonymized meat-plant hot-water surveys.

Narrative inputs

Current project submission: about 700 kWth, 18–21°C source and 145°C / approximately 4 bar(a) steam. The earlier IEA card gives 800 kW and a separate ammonia-side 12→7°C boundary; these are not one continuous operating range.

Heat pump solution

An ammonia screw heat pump and a pentane screw heat pump are coupled by a cascade heat exchanger. The pentane stage produces saturated steam for the prawn cooker. Both compressors are described as oil-lubricated screws adapted for the duty.

COP & savings

The earlier IEA card gives design heating COP 1.8 and combined COP 2.5, plus estimated CO₂ savings of 621 t/year. The new commissioning disclosure supplies no measured replacement values; the design figures are kept separate.

Investment / ROI notes

The card lists investment of €0.8 million excluding integration. It does not publish a payback. Savings in euro per year are left blank on the card.

FAQ

Is this a verified measured project?

No. Evidence level is public-source, from the IEA HPT / SPIRIT demo card and earlier SPIRIT slides. Design COP is not treated as independent field metering.

Why is this grouped with food cases rather than with the Central China meat plants?

The industry tag is food because the host plant cooks shrimp. The evidence tag stays public-source. The meat-plant pages remain anonymized field references for hot water, not steam.

What changed in the 2 November 2026 review?

Added the team’s commissioning disclosure and separated COP boundaries. The award submission is neither an award result nor an independent performance audit.