Taiji Fuling pharmaceutical plant, China: Dongfang Electric steam heat pump to 165°C
Dongfang Electric (3 Feb 2026 start-up): Dongfang Electric reports an 890 kW steam heat pump and booster at the Taiji Fuling pharmaceutical plant in Chongqing, China, lifting about 40°C waste heat to 165°C saturated steam at a stated COP of 2.7. Not independently metered here.
Run detailed calculation with this case一键代入详细计算
Engineering data
- Case type
- Public-source case — figures from published reports, papers, or vendor materials
- Data status
- Public-source case
- Data source
- China Heat Pump trade note, 9 Feb 2026: http://www.52chpc.com/show.php?itemid=88919 — industry reprint: https://iicnet.cn/article/7553 — Dongfang Electric, 3 Feb 2026: https://dfem.dongfang.com/info/1240/4031.htm
- Reviewer / date
- Editorial (Open Thermal AI) · 2026-11-02
- Industry
- Pharma
- Source temperature
- 40°C
- Sink temperature
- 165°C
- Temperature lift
- ≈ 125 K
- Heating or cooling duty
- 890 kW
- Architecture
- High-temperature steam heat pump plus a booster compressor; electric input reported near 330 kW for 890 kW heating
- Result status
- Dongfang Electric’s own 3 February 2026 announcement confirms commissioning at Taiji Fuling and reports about 330 kW electrical input, 890 kW rated heat and measured COP 2.7. This is a supplier report, not this site’s independent audit.
- Key risk
- Refrigerant, steam pressure, and annual hours are not in the short trade notes. A tonne-scale steam rate should not be read as a multi-megawatt boiler replacement.
- Existing system
- Pharmaceutical steam previously from natural gas or coal-fired boilers, as described in the trade reports; low-grade waste heat near 40°C
- Refrigerant
- Not stated in the trade reports used here
- COP
- 2.7
- Annual energy / emissions savings
- Not stated as a metered annual total in the reports used here
- Estimated payback
- Not disclosed in the reports used here
Project background
Dongfang Electric (Dongfang Electric Machinery) published a first installation of its high-temperature steam heat pump at the Taiji Fuling pharmaceutical plant in Fuling, Chongqing, China. This entry records that public note. It is not an author site survey.
Narrative inputs
Source: waste heat reported near 40°C. Sink: 165°C saturated steam. Rated heating capacity 890 kW with electric input near 330 kW, as stated in the trade reports.
Heat pump solution
A steam heat pump and booster recover low-grade waste heat and return saturated steam to the pharmaceutical process, displacing boiler steam for that duty. Architecture details beyond the booster arrangement are not in the short reports.
COP & savings
The reports state a COP of 2.7 at the large temperature lift and the 890 kW rating. No independent meter data, operating-hour total, or steam mass flow is reproduced here.
Investment / ROI notes
Capital cost and payback are not in the reports used here.
FAQ
Is this a verified measured project?
No. The original supplier announcement is now linked, but this site has not visited or metered the plant.
How should the 890 kW rating be read next to the 12 MWth paper-mill case?
Both are public-source process-steam entries, but the duties differ by about an order of magnitude. This pharmaceutical unit is a tonne-class steam package, not a large boiler replacement.
What changed in the 2 November 2026 review?
Added the original manufacturer source behind the earlier trade report. No later project-specific cumulative runtime or annual metered savings were located; this is stronger attribution, not a new operating milestone.