Huzhou Xisai: 2 MW air heat-pump storage reported at full load, steam near 540°C

Lüchu Technology (9 Apr 2026): a 2 MW-class very-high-temperature heat-pump storage demo at Xisai Science Valley, Huzhou, Zhejiang, China, reached full load. It uses air as the heat-pump fluid and molten salt as storage, and is reported to release superheated steam near 540°C at a COP of 1.41 from about 45°C waste heat. Not a process-steam heat pump, and not independently metered here.

Run detailed calculation with this case

Engineering data

Case type
Public-source case — figures from published reports, papers, or vendor materials
Data status
Public-source case
Data source
Lüchu Technology note via China Energy Storage Network, 13 Apr 2026: https://www.escn.com.cn/news/show-2246741.html — Manufacturer retrospective, 29 Jan 2026: https://www.lvchutec.com/newsinfo/10980848.html
Reviewer / date
Editorial (Open Thermal AI) · 2026-11-02
Industry
Manufacturing
Source temperature
45°C
Sink temperature
540°C
Temperature lift
≈ 495 K
Heating or cooling duty
2000 kW
Architecture
Reverse Brayton-style air heat pump charging molten salt, then releasing high-temperature steam — heat-pump storage, not closed-cycle steam generation plus MVR
Result status
The builders reported full-load operation on 9 Apr 2026. Electric input is about 1.5 MW and heating output about 2 MW. COP 1.41 is source-reported for the 45°C source. A separate 8 MW / 400°C phase was announced earlier and is not treated here as this operating unit.
Key risk
The April 2026 full-load account and a manufacturer retrospective of a February 2025 test give different dates and COPs. Their equipment/configuration relationship is not established here. Neither a short test nor a heat-pump COP proves annual storage-cycle performance.
Existing system
Demonstration of power-to-heat storage that can release industrial steam or support power generation; not described as a retrofit of one named process line
Refrigerant
Air (R729) as the heat-pump fluid; molten salt as storage
COP
1.41
Annual energy / emissions savings
Not stated as a metered annual total in the note used here
Estimated payback
Not disclosed

Project background

Huzhou Industrial Control Technology Research Institute and Zhejiang Lüchu Technology reported full load on a very-high-temperature heat-pump storage demo at Xisai Science Valley. The library keeps it under thermal storage. It can make steam, but the machine is an air heat pump charging molten salt.

Narrative inputs

Source about 45°C. Heating about 2 MW from about 1.5 MW electric. Reported steam about 540°C, salt about 565°C, compressor outlet 600°C-class, compressor inlet about 355°C.

Heat pump solution

Air is the heat-pump working fluid. Heat is stored in molten salt and can be released as high-temperature steam. The note also mentions uses in renewable curtailment and power-plant flexibility. Those uses are storage services, not a single process-steam retrofit.

COP & savings

Full load was reported on 9 Apr 2026 with COP 1.41 at a 45°C source. The same note says COP can exceed 2 if the waste-heat temperature is higher. No independent test record is reproduced here.

Investment / ROI notes

Capital cost and payback are not in the note used here.

FAQ

Is this a verified measured project?

No. Evidence level is public-source. Full-load and COP 1.41 are what the project developers reported. This site did not meter the unit.

Does the earlier 8 MW project belong in this entry?

No. An 8 MW / 400°C phase was a separate construction announcement aimed at later commissioning. This page records the 2 MW unit that was reported at full load in April 2026.

What changed in the 2 November 2026 review?

A manufacturer retrospective dated 29 January 2026 reports a 2 MW demonstration test in February 2025: 225 continuous full-power hours and COP 1.43. Keep this separate from the April 2026 account (COP 1.41) until unit identity and test boundaries are reconciled; do not treat 225 hours as annual operating hours.