Philip Morris Bologna: SPH two-stage heat pump supplies dryer steam at 139°C

SPH / JOA demo card (installation year 2025): at Philip Morris Manufacturing & Technology Bologna, a two-stage heat pump turns dryer exhaust heat into saturated steam at 139°C and 2.5 bar(g). Rated duty is 650 kW. A FAT COP of 2.5 is source-reported, not remeasured here.

Run detailed calculation with this case

Engineering data

Case type
Public-source case — figures from published reports, papers, or vendor materials
Data status
Public-source case
Reviewer / date
Editorial (Open Thermal AI) · 2026-11-02
Industry
Drying
Source temperature
36–50°C
Sink temperature
90–139°C
Temperature lift
≈ 40 K
Heating or cooling duty
650 kW
Architecture
Two-stage reciprocating heat pump (SPH) integrated by JOA with direct recovery from humid dryer exhaust
Result status
The card lists installation year 2025, about 5,000 h/a, and a COP of 2.5 measured during factory acceptance testing. That FAT figure is not a published multi-season site audit.
Key risk
COP 2.5 is a supplier-reported FAT value. The card’s 5,000 h/year is not evidence of cumulative site runtime. Do not merge the 650 kW dryer module with PMI’s separate Crespellano heat-pump/electric-boiler program or apply owner savings percentages to the whole Bologna operation.
Existing system
Industrial dryer with humid exhaust; process steam previously supplied from the site boiler plant
Refrigerant
R515B and R1233zd (two stages)
COP
2.5
Annual energy / emissions savings
Demo card reports about 3.9 GWh/year heat and 1.7 kt/year CO₂ savings; annual measurement period is not established in this review.
Estimated payback
Not disclosed; the card leaves investment and cost savings blank

Project background

Philip Morris Manufacturing & Technology Bologna published, via SPH and JOA, a dryer heat-recovery package that makes its own steam. The industry tag on this site is drying, so it can be filtered separately from food cooking and from paper-mill steam.

Narrative inputs

Source water 50°C → 36°C after exhaust recovery. Sink 90°C → 139°C saturated steam at 2.5 bar(g). Heating capacity 650 kW. Design operating time about 5,000 h/a.

Heat pump solution

Humid exhaust is recovered directly, then a two-stage heat pump lifts the residual heat, first toward 80°C and then to 139°C steam that returns to the dryer. Compressors are reciprocating. The integrator is JOA Air Solutions; the heat pump supplier is SPH.

COP & savings

COP 2.5 is explicitly a factory-acceptance measurement on the card, at the design point above. Annual heat delivery is given as about 3.9 GWh and CO₂ savings as about 1.7 kt/a. Investment is blank. PMI’s 17 March 2026 account locates the steam-heat-pump application at Zola Predosa and reports 40–50% lower primary fossil-steam demand and recovery of 30% of exhaust water. These owner figures are not an independent annual audit.

Investment / ROI notes

No investment or payback is published on the card used here.

FAQ

Is this a verified measured project?

No. Evidence level is public-source. The COP was measured during factory acceptance testing according to the supplier card, which is not the same as an independent site audit.

Why is the industry tag drying?

The published duty is steam returned to an industrial dryer. Drying is an existing filter on this library, separate from food and from general manufacturing.

What changed in the 2 November 2026 review?

Added the owner’s site-specific account and kept FAT, annual reference hours and reported savings separate. Obtain the matching metering period and system boundary before using these figures for a new project.