Trace the drive and working fluid to identify a unit. For a new project, check direct recovery first, then shortlist routes from site data.
Five routes you can distinguish on site
Classify by the main drive and the path of the refrigerant or process vapor. Hot water and steam describe the output, and air, wastewater and refrigeration reject heat describe the heat source. Several stages can be combined in one plant.
- Closed-cycle electric vapor compression. A motor drives a compressor in a separate refrigerant circuit. The heat is delivered through a condenser or gas cooler. Look for the compressor drive and trace the refrigerant loop on the drawing.
- Type I absorption heat pump. Higher-temperature heat, such as steam, drives a generator. The machine recovers lower-temperature heat and delivers useful heat at an intermediate level, typically from the absorber and condenser. Identify the driving-heat inlet, low-temperature source and useful-heat outlet.
- Type II absorption heat pump (heat transformer). A medium-temperature heat source supplies the generator and evaporator. The absorber delivers part of that heat at a higher temperature, and the condenser rejects heat at a lower temperature. Trace both the high-temperature delivery and the heat rejection circuit.
- Open-cycle mechanical vapor recompression (MVR). A mechanical compressor raises the pressure of the process vapor itself, for example secondary vapor from an evaporator, so it can supply heat again. Trace the vapor line through the compressor to the heat user.
- Steam-jet thermocompression (TVR). Higher-pressure motive steam entrains low-pressure vapor through a jet thermocompressor. The mixed discharge supplies useful heat at intermediate pressure. Verify the motive, suction and discharge lines and the point of use.
Engine- or turbine-driven compressors, adsorption cycles and combined systems also exist. Record the drive and fluid path for each stage when a single route does not describe the equipment.
Existing equipment: what confirms its type?
- Find the equipment tag and model. Match the nameplate to the manufacturer’s manual and the current piping and instrumentation diagram (P&ID). Check the drawing revision against the installed equipment.
- Confirm the main drive. Find what supplies the compressor shaft, absorption generator or steam-jet nozzle. Electrical power may run auxiliaries, and a steam line may serve the process or be on the discharge side.
- Trace the fluid and where its heat goes. Check where the line starts, where it goes and what flows through it. Confirm whether the compressor handles a separate refrigerant or process vapor. For absorption equipment, trace the driving heat, recovered heat, delivery and rejection to distinguish Type I and Type II. For a steam ejector, check that its discharge provides useful heat rather than only serving a vacuum system.
Record the outcome: confirmed when the documentation and installed connections agree, provisional when some evidence is missing, or unresolved when the evidence conflicts. Note drawing revision, equipment tag and what must be checked next. Use site-approved documents, installed instruments and authorized observations. Leave opening equipment or tapping live lines to qualified personnel under site procedures.
New projects: use field checks to build a shortlist
- Set the heat duty and test direct recovery first. Pick one process. Record the required medium, supply and return temperatures or steam state and pressure, load profile, and any hygiene or isolation constraints. For the source, record medium, inlet and minimum allowed outlet conditions, flow and timing. Check whether direct exchange can meet all or part of the duty after allowing for a heat-exchanger approach and simultaneous operation. Screen the remaining duty.
- Check for reusable process vapor. If it is available while heat is needed, record the suction and required delivery states, pressures (absolute or gauge), flow range, entrained liquid and contaminants. For evaporators, check boiling-point rise and heat-exchanger approach. Assess MVR if mechanical compression and the vapor path are feasible. Consider TVR as well if affordable motive steam is available at the required pressure and the process can use the mixed discharge. Follow the evaporation and concentration checklist for details.
- Check electric capacity and driving heat. With a separate heat source and sufficient electric capacity, check closed-cycle electric compression against the source and sink envelopes, including heat-exchanger approaches and part load. When higher-temperature driving heat and lower-temperature recoverable heat are both available during the duty, assess Type I absorption. When medium-temperature waste heat is available, only part needs a temperature upgrade, and a lower-temperature heat sink can accept the rejected heat, assess Type II absorption. Confirm actual temperatures, usable capacity, operating overlap and what the driving heat would otherwise be used for.
- Check integration and compare equivalent service. Compare the same useful heat delivered at the process, including backup and availability. Count electricity, driving heat or motive steam, auxiliaries, any added refrigeration load, and integration and maintenance costs. Check water quality, refrigerant and pressure safety, hygiene and downtime. A nameplate COP or a source temperature by itself cannot settle the choice.
Example: An evaporator has secondary vapor while its heating side needs steam. Record MVR as a candidate pending confirmation of vapor quality and the required pressure rise. Keep TVR pending until the pressure, availability and cost of motive steam are verified.
Write one row per route: candidate and reason · supporting evidence · missing data or constraint · next check. For readings, note the instrument or document, point, units, time and operating condition. Keep measured, documented and assumed values distinct. If a key condition is unknown, leave the route pending. Several routes can proceed to comparison. The shortlist does not establish feasibility or support procurement.
Technical references
- IEA HPT Annex 58 on high-temperature heat pump technologies and integration by source and sink conditions. Annex 58 final report
- Bakhtiari et al. on the two absorption cycles and how they integrate into industrial processes. Absorption heat pump retrofit study
- U.S. Department of Energy on recovering low-pressure vapor by recompression and on motive steam and mixed discharge. Steam Tip Sheet 11 · Steam Tip Sheet 29
识别现有机组,先查靠什么驱动、工质流向哪里。新项目先看余热能否直接利用,再用热源、用热需求和公用工程条件筛出候选路线。关键资料缺失时,先补确认或补测。
现场可以区分的五条路线
按主要驱动方式和制冷剂或工艺蒸汽的路径来分。热水和蒸汽描述供热产物,空气、废水和制冷排热描述热源。同一套系统也可能串联多级不同路线。
- 闭式电驱蒸气压缩热泵。 电机带动压缩机,制冷剂在独立回路内循环,通过冷凝器或气体冷却器供热。查压缩机驱动,在图纸上沿制冷剂回路核对流向。
- Ⅰ类吸收式热泵。 较高温的热量(例如蒸汽)驱动发生器,同时回收较低温热源,通常由吸收器和冷凝器输出中间温度的有用热量。核对驱动热入口、低温热源和供热出口。
- Ⅱ类吸收式热泵(吸收式热变换器)。 中温热源给发生器和蒸发器供热,吸收器把其中一部分热量提升到更高温度,其余热量通过冷凝器向低温侧排放。查清高温供热和低温排热两条回路。
- 开式机械蒸汽再压缩(MVR)。 机械压缩机对工艺蒸汽本身升压,例如蒸发器的二次蒸汽,再送去供热。沿蒸汽管追踪压缩机入口、出口及用热点。
- 蒸汽喷射式热压缩(TVR)。 用高压动力蒸汽通过喷射器引射低压蒸汽,混合后以中间压力输出供热。核对动力蒸汽、被引射蒸汽、混合出口及用热点。
还有发动机或汽轮机驱动的压缩式、吸附式和组合系统。看到多级组合时,逐段记录每一级的驱动和工质路径。
现有机组:用什么证据确认类型?
- 先找设备位号和型号。 用铭牌对照厂家手册和现行管道及仪表流程图(P&ID),核对图纸版本与现场接管。
- 确认主要驱动。 查压缩机轴由什么带动,或者哪股热流进入发生器、哪路动力蒸汽进入喷嘴。电源也可能只供辅机,蒸汽管也可能是工艺用汽管或供汽出口。
- 沿管路确认工质与热量去向。 记下起点、终点和介质,确认压缩的是独立回路的制冷剂还是工艺蒸汽。吸收式要查驱动热、回收热、供热和排热去向以区分Ⅰ类、Ⅱ类。蒸汽喷射器还要确认出口是否供热,仅用来抽真空的喷射器另行记录。
记录判断: 资料和现场接管相符时记为「已确认」,只有部分线索时记为「初步判断」,证据冲突时记为「待核实」。留存位号、图纸版本和待核项。用经批准的资料、现有仪表和授权巡检取证。拆检或在带压管线上开口取样,应由有资质人员按现场规程执行。
新项目:怎样通过点检筛出候选路线?
- 圈定用热任务,先查能否直接回收。 选定一道工序,记录用热介质、供回水温度或蒸汽状态与压力、负荷变化和卫生隔离要求。热源侧记介质、入口与最低允许出口条件、流量和运行时段。计入换热端差和运行重叠,先看直接换热能覆盖多少,只对剩余任务评估升温路线。
- 查有没有可再利用的工艺蒸汽。 如果用热时有可用蒸汽,记录吸入与所需出口状态、压力(绝压或表压)、流量范围、夹液和杂质。蒸发工序另查沸点升高与换热端差。机械压缩与蒸汽回用条件满足时评估 MVR。有压力合适、成本可接受的动力蒸汽,且工艺能使用混合出口蒸汽时,也评估 TVR。详见蒸发浓缩点检。
- 查剩余电容量和可用驱动热。 有独立热源和足够电容量时,把闭式电驱压缩式列入候选,核对热源与用热侧的运行范围、换热端差及部分负荷。有较高温驱动热和较低温可回收热,且与用热同步时,评估Ⅰ类吸收式。有中温余热,只需把部分热量升温,且有低温侧能接收排热时,评估Ⅱ类吸收式。核实实际温度、可用热量、重叠时段及驱动热原本能作什么用。
- 查接入条件,按同等供热比较。 以工序收到的同等有效热量、供热可用率和备用要求为基准,计入电、驱动热或动力蒸汽、辅机、原制冷系统可能增加的电耗,以及接入和维护费用。核查水质、工质及压力安全、卫生与停机条件。单看铭牌 COP 或热源温度无法定路线。
示例: 蒸发器有二次蒸汽,同一时段加热侧仍需用汽。先把 MVR 列为候选,下一步核对二次蒸汽品质和所需升压。TVR 先记为待确认,补查动力蒸汽压力、可用量和成本。
每条路线记一行: 候选及理由 · 支持证据 · 缺项或制约 · 下一项核对。读数写明仪表或资料、测点、单位、时间和工况,区分实测、资料记录和假设。关键条件未知就保留为待确认;符合初筛条件的多条路线可同时比较。点检结果只支持路线初筛,采购前还需复核设备运行包络和工艺安全。
技术依据
- IEA HPT Annex 58 介绍高温热泵路线及按热源、用热条件开展集成的方法。Annex 58 最终报告
- Bakhtiari 等人研究了两类吸收循环及其在工业工艺中的集成。吸收式热泵改造研究
- 美国能源部介绍低压蒸汽再压缩、动力蒸汽及混合出口。蒸汽技术资料第 11 号 · 蒸汽技术资料第 29 号