項目中心 · 年運行匹配

年負荷重疊小時、儲熱與換熱器 vs 熱泵

Screening benefits are limited by how often waste heat and heat demand overlap—not by rating × 8760. Direct heat exchange mostly moves waste heat to users; a closed booster heat pump adds compressor electricity into the useful heat, so the bill must subtract that power. Pair with 創建項目 overlap fields and heat exchangers.

1 · 重疊小時是什麼

Overlap hours answer: in one year, how many hours are waste heat and useful-heat demand both present? Only that window feeds the annual energy account in Project Center screening.

重疊 ≠ 工廠運行小時

A factory may run many hours with refrigeration on but no hot-water draw—or hot water needed while the refrigeration plant is off. Those hours do not count as overlap.

低 / 中 / 高負荷分檔

Project Center splits overlap into three load bins for screening (not a weather forecast term). Defaults scale design waste-heat availability and heat demand (about 0.6× / 1.0× / 1.1× on the source side and 0.5× / 1.0× / 1.1× on demand). Each bin contributes roughly min(available, demand) × hours.

三檔合計

低 + 中 + 高重疊小時之和,纔是年可對齊熱量所用的時間窗。合計 ≤ 8760,也不應超過已確認的年度可用小時。除非現場幾乎全年時刻對齊,不要把三檔都填滿接近 8760。

2 · 舉例:氨製冷排熱 → 工藝熱水

Food plant: design recoverable reject heat ≈ 500 kW; design hot-water demand ≈ 400 kW. Illustrative overlap bins (similar to Project Center demos):

分檔 小時/年 典型場景
低 800 h 夜間/週末:兩邊都有一點,但都不大
中 2 500 h 白班正常:排熱與熱水大致同時出現
高 1 200 h 旺季高峯:重疊時段兩邊都偏滿負荷

Sum ≈ 4 500 h/year. The remaining ~4 000+ hours are often misaligned or idle—they do not enter the annual useful-heat total by default. Filling medium as 8 760 would roughly double the paper savings.

3 · 直接換熱器 vs 閉式增壓熱泵

The same overlap window feeds annual hours, but what the user receives and what the bill must subtract depend on recovery topology.

A · 直接換熱器(溫度已經夠)

Useful heat to the sink ≈ heat taken from the waste-heat stream (after approach / losses). Almost no booster electricity. Outlet temperature cannot meaningfully exceed the source condensing / saturation temperature minus approach—see heat exchangers. Prefer HX when temperatures allow; keep it as the fair baseline against booster options.

B · 閉式增壓熱泵(需要抬溫)

Steady-state intuition (losses aside): Quseful ≈ Qfrom waste heat + Welectric, or COP ≈ Quseful / Welectric. Electricity both increases useful heat and adds cost. Benefits must subtract booster kWh × tariff (plus any refrigeration power penalty and recovery auxiliaries, minus condenser-fan savings). Project Center uses an incremental boundary vs incumbent heat—not “free heat from COP”.

C · 混合(先換熱,不夠再熱泵)

能直接換的先換(無/少抬溫電);缺口或更高溫度段再上閉式增壓熱泵。負荷跨溫區時往往更省。

項目 直接換熱器 增壓熱泵
廢熱去哪 經換熱器到用熱 進熱泵蒸發器
用電去哪 基本無(或極少輔機) 進壓縮機,最終也進用熱
用熱從哪來 ≈ 廢熱 ≈ 廢熱 + 電
重疊小時作用 限制「能搬多久」 限制「能搬 + 能抬溫多久」
效益敏感點 溫差/流量是否真換得動 COP、電價、抬溫是否值得買單

One-sentence memory: a heat exchanger moves waste heat; a heat pump moves waste heat and folds electricity into useful heat—so never credit the extra heat without the power cost.

4 · 儲熱何時有用

Storage addresses time misalignment. It does not turn 4 500 overlap hours into 8 760.

沒有儲熱時

某一檔裏廢熱多於用熱,多出來的熱量記爲未用熱量,年可對齊熱量與節能量下降。

有儲熱(換熱器路徑)

可把當時用不完、已回收的熱存起來,等用熱回來再放——受儲熱容量(kWh)與充放可行性限制。

有儲熱(熱泵路徑)

Storage still mainly shifts thermal timing. Electricity is still paid when the booster runs. Do not assume “heat in the tank means the kWh were free.” Screening may credit a limited recovery of unused heat from storage capacity; fine dispatch and cycle counts are not fully monetized without more data.

儲熱不夠時

若重疊長期很少,單靠加大儲熱往往救不了經濟性——先確認工藝用熱能否真正接住廢熱品位與時間表。

Need a capacity-level tank size? Open the 儲熱計算 Agent (water sensible screening). For stratified-tank physics, use ASWT.

5 · 項目中心字段怎麼填

嚮導「運行重疊」步驟的實用順序。

  • Judge temperature first: if direct HX can meet the sink, think overlap as “hours both streams are present for exchange.”
  • If a booster is required: still enter hours when waste heat and heat demand coexist. Do not inflate overlap because electricity also becomes heat.
  • Split low / medium / high: when unsure, put most hours in the medium bin; keep the sum honest.
  • Storage: fill capacity when shifts clearly misalign; otherwise leave blank and read the no-storage baseline first.
  • Read results by topology: HX path → matched heat; booster path → matched useful heat minus incremental electricity cost.

Open 創建項目 (phase-change / reject-heat path), size storage with the 儲熱計算 Agent, or return to the 項目中心.

6 · 常見問題

「所以大概只有合計約 4 500 h 算進效益?」

對初篩年可對齊熱量的時間窗而言是的。儲熱可有限挽回「當時有熱但沒用上」的一部分——不能憑空變成全年對齊。

「熱泵路徑用熱不是比廢熱還多嗎?」

Yes: Quseful ≈ Qfrom source + Welectric. That extra heat is paid for as electricity. Incremental COP and net benefit already treat power as a cost, not free energy.

「能把工廠年運行小時填進重疊字段嗎?」

不要。請填廢熱與用熱重疊的小時。顯熱單相路徑可能另用年運行小時;相變/排熱初篩要的是重疊分檔。

「本站下一步看哪裏?」

創建項目 · 換熱器 · 循環導讀 · 知識庫總覽.

本頁重疊分檔、儲熱與拓撲用電邊界對齊 Open Thermal AI 項目中心初篩直覺。不能替代實測負荷曲線、廠家性能圖或合同級能耗模型。