熱泵小知識 · 製冷劑
製冷劑知識指南
A structured, illustrated map of refrigerant history, today's transition, and regional law—for heat pump engineers, buyers, and decision-makers. For fluid properties see the working-fluid table or the 本站物性計算 (PT/PH/PQ, P–h envelope); for project compliance always verify the current consolidated text in your jurisdiction. Not legal advice.
1 · 製冷劑發展史與代際
Refrigerant choice has always been a stack of thermodynamics, safety, cost, and regulation. The “generations” below overlap in time—industrial ammonia and CO₂ never left the field even as CFCs and HFCs dominated comfort HVAC.
圖中的英文標註
- Montreal Protocol
- 《蒙特利爾議定書》
- Kigali Amendment
- 《基加利修正案》
| 代際 | 年代 | 代表工質 | ODP | GWP(100 年) | 熱泵應用 | 主要驅動力 |
|---|---|---|---|---|---|---|
| 天然工質(合成前) | 1830 年代至今 | R717 (NH₃), R744 (CO₂), R718 (H₂O), SO₂ (historic) | 0 | 0–1 | 工業/高溫熱泵;CO₂ 跨臨界;氨工藝供熱 | 效率與成本;臭氧與氣候政策推動復興 |
| 1st — CFC | 1930s–1990s | R11, R12, R502 | 高(0.6–1.0) | 4,000–10,000+ | 遺留冷水機;已基本淘汰 | 《蒙特利爾議定書》ODS 淘汰 [1] |
| 2nd — HCFC | 1990s–2020s | R22, R123, R142b | 低–中(0.01–0.11) | 100–2,000 | R22 熱泵/冷水機(遞減);改造市場 | 議定書 HCFC 削減時間表 [1] |
| 3rd — HFC | 1990 年代至今 | R134a、R410A、R407C、R404A、R245fa | 0 | 675–4,000+ (R410A ≈2088) [3][4] | 舒適與商用熱泵主流;工業中高溫 | ODS 替代;現受基加利與 F-gas 約束 [1][7][8] |
| 4th — HFO / low-GWP blends | 2010 年代至今 | R1234yf、R1234ze(E)、R1233zd(E)、R32、R454B、R454C、R515B | 0 | <1 至 ~700(視工質)[3][4] | R410A 替代(R32/R454B);高溫 R1233zd(E);復疊高溫級 | 基加利、歐盟 F-gas、AIM 法案;PFAS 監管帶來不確定性 [1][7] |
| 天然工質復興(並行) | 2000 年代–未來 | R744, R717, R290, R600a, R718 | 0 | ≤3(CO₂=1) | CO₂ 熱泵(含極寒復疊);氨工業熱泵;丙烷商用 | 氣候政策、充注限制、IEA/行業脫碳路線 [5][6] |
ODP/GWP:ANSI/ASHRAE Standard 34 與 2021 ASHRAE Handbook—Fundamentals 第 29 章 [3][4]。項目數值以製造商資料爲準。
2 · 現狀與未來方向
Two transitions run together: heat pump deployment at scale (driven partly by Paris NDCs and electrification [2]) and refrigerant switching (driven by Kigali and national F-gas law [1][7][8]).
建築與商用 HVAC
R410A → R32 / R454B / R454C is the dominant comfort-HP transition in many markets. The EU F-gas revision caps new split AC at GWP ≤750 from 2025 under Regulation (EU) 2024/573 [7]; Singapore NEA targets GWP ≤150 for new commercial refrigeration from July 2027. In the U.S., EPA Technology Transition rules under the AIM Act restrict high-GWP HFCs in new products by sector [8]—read together with SNAP end-use listings and stricter state rules (e.g. California CARB).
工業與高溫熱泵
Industrial duty spans CO₂ (R744), ammonia (R717), propane (R290), HFOs such as R1233zd(E), and legacy HFCs (R245fa, R134a) in installed base. IIR Technical Brief No. 61 (2026) maps fluids for roughly 90–300 °C industrial decarbonisation [5]. Transition is slower than comfort HVAC because of charge size, safety class, and process integration—but policy pressure is building in parallel with demonstration projects reported at the 15th IEA Heat Pump Conference (Vienna, May 2026) [6].
PFAS 與有機氟化學品不確定性
Many HFOs and some HFC blends sit in broader PFAS / organofluorine regulatory debates—EU REACH restriction proposals and U.S. TSCA actions are not identical to F-gas quotas but can affect 15-year fluid strategy. Treat low-GWP HFO selection as a chemistry risk item, not only a GWP checkbox [7].
IEA 與行業展望
IEA analysis ties heat pump growth to grid decarbonisation and policy support; refrigerant transition is a stated enabler, not a side topic [6]. Expect parallel tracks: natural fluids and fourth-generation blends in new equipment, tighter service/reclaim rules on high-GWP banks, and more standardised test methods for low-GWP systems.
3 · 國際政策框架
Four treaties are often named together—but only Montreal and Kigali directly regulate refrigerants. Kyoto and Paris shape the electrification and decarbonisation context that drives heat pump adoption [1][2].
| 文件/條約 | 年份 | 與製冷劑直接關係 | 對熱泵行業影響 |
|---|---|---|---|
| 《蒙特利爾議定書》 | 1987 | 直接連接 — phases out ODS (CFCs, HCFCs) on Annex schedules [1] | 推動 HFC 大規模替代 ODS;HCFC 存量持續削減 |
| 《基加利修正案》 | 2016 | 直接連接 — HFC production/consumption phasedown for ratifying Parties [1] | 低 GWP 工質與天然工質成爲合規主方向 |
| 《京都議定書》 | 1997 | Indirect — quantified GHG targets for developed countries [2] | 提高 HFC 氣候影響關注度;爲基加利 HFC 行動鋪墊 |
| 《巴黎協定》 | 2015 | Indirect — NDCs, net-zero pledges [2] | 供熱電氣化;熱泵作爲脫碳工具與電網清潔化並行 |
基加利 HFC 削減時間表 [1]
Percentages are relative to each group's agreed HFC baseline (CO₂-eq). A5 includes China, India, and most developing countries—baseline years 2020–2022, with an initial freeze in 2024–2028 before step-downs begin.
| 締約方組別 | 基線年 | 2019–2023 | 2024–2028 | 2029–2033 | 2034–2036 | 最終階段 |
|---|---|---|---|---|---|---|
| A1 組(含歐盟、美國、日本) | 2011–2013 | 基線的 90% | 60% | 30% | 20% | 2036 年起 15% |
| A5 組(含中國) | 2020–2022 | 基線(100%) | 凍結於基線 | 90%(2029 起減 10%) | 2033 年累計減 50% | 2045 年降至 20%(減 80%) |
4 · 中國 · 歐盟 · 美國 — 過去 · 現狀 · 未來
Kigali sets outer bounds; national and state law decides what you must comply with on each shipment. Dates below are orientation markers—verify consolidated texts before quoting in contracts [7][8][9].
圖中的英文標註
- China
- 中國
- EU
- 歐盟
- United States
- 美國
- Past (1987–2014)
- 過去(1987–2014)
- Present (2015–2025)
- 現狀(2015–2025)
- Future (2026–2036+)
- 未來(2026–2036+)
過去(1987–2014)
| Dimension | 中國 | 歐盟 | 美國 |
|---|---|---|---|
| 臭氧層(ODS) | 履約《蒙特利爾議定書》;HCFC 生產/消費凍結與削減,配合附件調整 [1][9] | 歐盟 ODS 法規;設備 fleet 自 CFC → HCFC → HFC 過渡 [1] | 《清潔空氣法》第六章;SNAP 替代物清單開始塑造可用工質 [1][8] |
| 氣候(基加利前) | 京都時代對 HFC 氣候影響關注上升;國標向能效方向演進 [2] | 2015 年 F-gas 法規 517/2014 生效——HFC 配額體系 [7] | 州法先行於聯邦 HFC 規則;EPA SNAP 分行業規則擴展 [8] |
現狀(2015–2025)
| Dimension | 中國 | 歐盟 | 美國 |
|---|---|---|---|
| HFC 削減 | Kigali in force 9 Sep 2021; MEE HFC production/import quota system with annual allocations [1][9] | 517/2014 quota cuts; 2024/573 revision tightens product bans & leakage rules—check consolidated text [7] | AIM Act (2020); EPA phasedown rules (40 CFR Part 84); Technology Transition Rule by sector [8] |
| 產品/市場規則 | GB 能效標識;GB/T 45650-2025 CO₂ 熱泵國標;產品監督推動更低 GWP [10] | New split AC GWP ≤750 from 2025; UK F-Gas parallel but separate post-Brexit [7] | Federal GWP limits vary by sector; California CARB and other states often stricter [8] |
| 化學品平行賽道 | 化學品管控演進中;PFAS 範圍與歐盟 REACH 尚不對等 [7] | REACH PFAS 限制提案給部分 HFO 帶來中長期不確定性 [7] | TSCA PFAS 報告/限制;須與 F-gas 規則一併閱讀 [8] |
未來(2026–2036+)
| Dimension | 中國 | 歐盟 | 美國 |
|---|---|---|---|
| HFC 軌跡 | 配額隨 A5 組時間表收緊(2045 年減 80%);天然工質國標體系完善 [1][9] | F-gas 配額進一步削減;PFAS 限制或影響 HFO 供應鏈 [7] | EPA 後續 AIM 階段;州級更快禁止新高 GWP 設備 [8] |
| 熱泵方向 | Industrial HP policy push + natural fluids (CO₂, R290, NH₃); see policy map [9][10] | 更多應用轉向天然工質與 GWP<150 混合工質;工業熱泵納入脫碳包 [5][7] | 電氣化激勵 + HFC 削減推動低 GWP 熱泵產品線;工業應用增長 [6][8] |
分用途里程碑(示例——請本地核實)
| 應用場景 | 中國 | 歐盟 | 美國 |
|---|---|---|---|
| 新分體空氣源熱泵 | 配額 + 產品標準向低 GWP 傾斜;尚無歐盟式全國統一產品 GWP 上限——跟蹤生態環境部與市場監督管理總局動態 [9] | GWP ≤750 for new split AC from Jan 2025 (2024/573) [7] | EPA 技術轉換:分行業 GWP 限值;多數新建住宅/輕型商用空調脫離 R410A 類工質 [8] |
| 商用冷水機/屋頂機 | HFC 配額影響供應;新設備 R32/R410A 切換進行中 [9] | F-gas 產品清單禁止多類固定式應用使用高 GWP HFC [7] | SNAP + AIM 分行業規則;按冷水機類型查 EPA 清單 [8] |
| 工業/高溫熱泵 | CO₂、NH₃、R290、HFO 路線;GB/T 45650-2025 CO₂ 熱泵 [5][10] | 傾向天然工質;大充注須許可與安全規範 [5][7] | 氨/CO₂ 工業基礎成熟;高溫熱泵 HFO 應用增加 [5][8] |
| 維保/回收 | HFC 消費受配額約束;回收體系擴展 [9] | 部分設備禁止高 GWP 原裝工質維保;泄漏檢測閾值收緊 [7] | AIM 分配 + 回收要求;州法或追加規定 [8] |
5 · 熱泵選型與合規實務
Before locking a fluid for a 15-year plant, walk this sequence—then cross-check against the property table and destination law.
- Define the application band: source/sink temperatures, lift, capacity swing, and whether duty is comfort, process, or high-temperature industrial [5].
- Screen fluids by physics: critical temperature, pressure envelope, glide, material compatibility—use ASHRAE Std 34 data [3][4].
- Classify safety: toxicity and flammability (A1/A2L/A3/B2L etc.); charge limits and room volume rules drive site layout [3].
- Map every destination market: where equipment is sold, installed, and serviced—China, EU, US federal, and strictest state (e.g. California) may differ [7][8][9].
- Plan the 15-year path: virgin fluid availability, reclaim, spare parts, and whether PFAS/chemistry policy affects your HFO choice [7].
一句話記憶
Physics picks what can work; the jurisdiction you ship to and service in picks what may be sold and maintained—map Kigali first, then national instruments, then your safety case.
常見問題
“Is R-410A banned on the same calendar worldwide?”
No. Even where HFC phasedowns exist, application lists, grace periods, and servicing rules differ by region. One date in one regulation is not automatically global law [7][8][9].
「選了氨或 CO₂,就自動不受 F-gas 那類規則管嗎?」
You avoid most HFC quotas, but still face pressure-equipment, toxicity/charge, occupational safety, and possibly chemical policy for other fluorinated products on site [3][7].
「內銷與外銷——工質標籤能一樣嗎?」
Often 否. China in-country labels, EU CE/F-gas requirements, and US EPA certification paths can diverge for the same compressor platform—build a compliance matrix per SKU [7][8][9].
「工業現場 HFC 大充注——還能一直補加嗎?」
Quota and service rules are tightening globally. Plan reclaim, retrofit, or fluid change before virgin supply or legal service windows close for your fluid [1][7][9].
「中國工業熱泵政策從哪裏查?」
Pair this guide with the site industrial heat pump policy map for national action plans, carbon assessment, and natural-fluid direction [9].
6 · 主要參考文獻
Numbered sources cited in this guide. Verify dates and thresholds against current consolidated legal texts before contract or compliance use.
- [1] UNEP Ozone Secretariat — 《蒙特利爾議定書》 & 《基加利修正案》 texts, handbooks, and party data.
- [2] UNFCCC — 《京都議定書》; 《巴黎協定》 (climate framework context).
- [3] ANSI/ASHRAE Standard 34-2022 — Designation and Safety Classification of Refrigerants.
- [4] 2021 ASHRAE Handbook—Fundamentals 第 29 章 — 常用製冷劑 ODP/GWP 數據。
- [5] IIR Technical Brief No. 61 (2026) — High-Temperature Heat Pumps for Industrial Decarbonisation.
- [6] IEA — Heat Pump Centre reports; 15th IEA Heat Pump Conference (Vienna, May 2026) public summaries.
- [7] EU — Regulation (EU) 2024/573 (F-gas revision); REACH PFAS restriction process.
- [8] U.S. EPA — AIM Act HFC phasedown; SNAP Program; 40 CFR Part 84.
- [9] China MEE — HFC production/import quota management measures and annual quota announcements (生态环境部 HFC 配额管理).
- [10] GB/T 45650-2025 — Carbon dioxide air source heat pump units (see also standards quick reference).
Orientation only — not legal advice. Verify current consolidated texts before quoting ban dates or GWP thresholds in contracts.
製冷劑百科
常用熱泵工質
Reproduces Table 2 from the IIR Technical Brief A Key Technology for Industrial Decarbonisation (61st IIR Technical Brief, 2026), with additional rows for common HVAC heat-pump fluids (R-32, R-410A, R-454B, R-454C) from ASHRAE Standard 34. For fluid screening and safety-class orientation only—confirm against manufacturer data and site regulations.
熱泵工質物性(IIR 表 2 + ASHRAE 34 補充)
| TYPE | REFRIGERANT | 化學名稱(中英對照) | FORMULA | tcr (°C) | pcr (MPa) | NBP | ODP | GWP | SAFETY |
|---|
IIR Table 2 data from [31] and [32], unless otherwise specified. a: [33], b: [34], c: [35], d: [36], e: [37]. Rows marked f (R-32, R-410A, R-454B, R-454C, R-134a, R-245fa, R-142b, R-515B): ANSI/ASHRAE Standard 34 Tables D-1/D-2; 2021 ASHRAE Handbook—Fundamentals, Ch. 29 Tables 3–5 (GWP100). Chemical names and compositions: ANSI/ASHRAE Standard 34-2022 Refrigerant Designations.
R&D roadmap & adoption barriers → 高溫熱泵專欄